a Phillips screwdriver,
▪
the necessary amount of electrical wires and appropriate wiring tools.
For more information on what wires to use, see
2.4.2 About the location of the terminals
Understand the arrangement of terminals and the location of openings on the
module and plan how to route the cable and in which order to connect its wires to
facilitate the installation procedure.
For connection details see
j i
c
b
a
e
d
h
g
f
l
k
a
Live terminal 230 V AC
b
Neutral terminal 230 V AC
c
Earth terminal
d
Power supply output 24 V DC (+)
e
Power supply output 24 V DC (–)
f
Contact input 24 V DC (+)
g
Contact input 24 V DC (–)
h
Earth terminal
i
Ethernet connection (A) Refer to Setup types in
"8 Appendix A – About detecting
the IP address of the Security gateway"
35] For correct wiring
J
Ethernet connection (B) Refer to Setup types in
"8 Appendix A – About detecting
the IP address of the Security gateway"
35] For correct wiring
k
"DC_OK" LED (DC_OK)
l
"PWR" LED (PWR)
2.5 To install the 2 Security gateway hardware components
The Security gateway modules are to be mounted onto a 35 mm DIN rail.
1
Place the module over the top of the DIN-35 rail so that the upper hook on the
rear face is hooked in.
2
Push the module in direction (a) until the lower hook snaps into the rail.