OMM 1087
AGZ 025D through 190D
17
Unit Level Setpoints:
Description Default
Range
Mode/Enabling
Unit Enable
Enable
Disable, Enable
Network Unit Enable
Disable
Disable, Enable
Control source
Local
Local, Network
Available Modes
Cool
Cool, Cool w/Glycol, Cool/Ice w/Glycol
Ice, Test
Network Mode Command
Cool
Cool, Ice
Staging and Capacity Control
Cool LWT 1
7°C (44.6°F)
See Auto Adjusted Ranges, page 19
Cool LWT 2
7°C (44.6°F)
See Auto Adjusted Ranges, page 19
Ice LWT
4.4°C (39.9°F)
-9.5 to 4.4 °C (14.9 to 39.9 °F)
Network Cool Set Point
7°C (44.6°F)
See section 5.1.1
Network Ice Set Point
4.4°C (39.9°F)
-9.5 to 4.4 °C (14.9 to 39.9 °F)
Startup Delta T
5.6°C (10.1°F)
0.6 to 8.3 °C (1.1 to 14.9 °F)
Shut Down Delta T
0.3°C (0.5°F)
0.3 to 1.7 °C (0.5 to 3.1 °F)
Max Pulldown
0.6°C/min (1.1°F/min)
0.1 to 2.7 °C/min (0.2 to 4.9 °F/min)
Nominal Evap Delta T
5.6 °C (10.1°F)
3.3 to 8.9 °C (5.9 to 16 °F)
Demand Limit Enable
Off
Off, On
Network Capacity Limit
100%
0 to 100%
LWT Reset Enable
Off
Off, On
Configuration
Power Input
Single Point
Single Point, Multi Point
Evap Control
#1 Only
#1 Only, #2 Only, Auto,
#1 Primary, #2 Primary
Number of Compressors
4
4,6
Expansion Valve Type
Thermal
Thermal, Electronic
Fan VFD enable
No
No, Yes
Number of fans 4
4,6,8,10,12,14
Timers
Evap Recirc Timer
30
15 to 300 seconds
Stage Up Delay
240 sec
120 to 480 sec
Stage Down Delay
30 sec
20 to 60 sec
Stage Delay Clear
No
No, Yes
Start-start timer
15 min
10-60 minutes
Stop-start timer
5 min
3-20 minutes
Clear Cycle Timers
No
No, yes
Ice Time Delay
12
1-23 hours
Clear Ice Timer
No
No,Yes
Sensor Offsets
Evap LWT sensor offset
0°C (0°F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
Evap EWT sensor offset
0°C (0°F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
OAT sensor offset
0°C (0°F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
Alarm Settings
Low Evap Pressure Unload
689.5 KPA(100 PSI)
See section 5.1.1
Low Evap Pressure Hold
696.4 KPA(101 PSI)
See section 5.1.1
High Condenser Pressure
4240 KPA(615 PSI)
3310 to 4275 KPA (480 to 620 PSI)
Continued next page.