IOM 1210-7 • MAGNITUDE
®
MODEL WMC CHILLERS
48 www.DaikinApplied.com
o
peraTIon
WATER Setpoints
Figure 49: WATER Setpoint Screen
Table 17: WATER Setpoint Settings
Description
Default
Range
Password
Comments
Maximum Reset Delta T
0.0°F
0.0 to 20.0 °F
M
Set the maximum reset that can occur, in degrees F if LWT reset is selected or max
reset at 20 mA input if 4-20 mA is selected in SP7
Start Reset Delta T
10.0°F
0.0 to 20.0 °F
M
Sets the evap delta-T above which Return reset begins
LWT Reset Type [SP7]
NONE
NONE, RETURN,
4-20mA
M
Select reset type, NONE for none, RETURN for resetting chilled water based on
the entering water, or 4-20 mA for external analog signal
Templifier Source Reset:
55°F
50 to 100°F
M
Sets maximum Delta T allowed between active LWT SP and evaporator LWT.
Active LWT SP is lowered as necessary to prevent exceeding this value.
Templifier Source No Start:
70°F
30 to 100°F
M
Entering evaporator water temp below which Templifier will not start.
Stage Delta T
1.0
0.5 to 5°F
M
Sets the temperature the leaving water must be above setpoint for next
compressor to start
Startup Delta T
3.0°F
0.0 to 10.0 °F
M
Degrees above setpoint for chiller to start
Shutdown Delta T
3.0°F
0.0 to 3.0 °F
M
Degrees below setpoint for chiller to stop
Leaving Water Temp - Cool
44.0°F
35.0 to 80.0 °F
M
Evaporator LWT setpoint in COOL mode
Leaving Water Temp - Heat
135.0°F
110 to 135°F
M
Condenser LWT setpoint in HEAT mode
Leaving Water Temperature (LWT) Reset
The Active Leaving Water variable shall be set to the current
Leaving Water Temperature (LWT) setpoint unless modified
by one of the reset methods below. (The current LWT setpoint
is Cool LWT as determined by the chiller mode.) The type of
reset in effect is determined by the LWT Reset Type setpoint
(Setpoint 7 of the WATER Setpoint Screen). It is important to
note that all reset functions are designed with a filter to prevent
chiller shutdown in the case of a sudden delta change.
Reset Type – NONE
The Active Leaving Water variable is set equal to the current
LWT setpoint, determined by the Unit mode.
Reset Type – RETURN
(Cool Mode)
The Active Leaving Water variable is adjusted by the return
water temperature.
When the chiller mode = COOL, the Active Leaving Water
variable is reset using the following parameters:
Содержание Magnitude
Страница 4: ......
Страница 23: ...Installation www DaikinApplied com 21 IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS...
Страница 24: ...IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS 22 www DaikinApplied com Installation Figure 20 Wiring Index...
Страница 25: ...Installation www DaikinApplied com 23 IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS...
Страница 26: ...IOM 1210 7 MAGNITUDE MODEL WMC CHILLERS 24 www DaikinApplied com Installation Figure 21 Controller Box Wiring...