IOM 1266-2 • MAGNITUDE
®
MODEL WME CHILLERS
36 www.DaikinApplied.com
o
peraTIon
Figure 43: Settings View - Motor
Table 15: Motor Setpoints
Description
Default
Range
PW
Comments
Dual to Single Target
-30
-5 to -100
T
Hysteresis for staging compressors up or down based on the efficiency curves
Single to Dual Target
30
5 to 100
T
Dual to Single Factor
1.0
0.7 to 1.3
T
Scaling factor when transitioning from dual to single compressor operation
Single to Dual Factor
1.0
0.7 to 1.3
T
Scaling factor when transitioning from single to dual compressor operation
Stage Transition Target
1.0
.8 to 1.2
T
Scaling factor for transitioning compressors based on efficiency curves
Nameplate RLA
(VFD Load Side)
Factory set
Model dependent
T
Sets the Rated Load Amps (RLA) per compressor phase as given on the chiller
nameplate - Load Side Phase Data.
Maximum Amps
100%
70 to 100%
O
Inhibits capacity increase above %RLA. Unloading forced at 5% above value.
Demand Limit Enable
OFF
ON, OFF
O
ON: Limits % RLA to a value set by the Demand Limit analog input,
where: 4 mA = 100% RLA
20 mA = Minimum Demand Limit Setpoint
OFF: The Demand Limit input is ignored.
Harmonic Filter Amp Rating
Factory set
Model dependent
T
Based on model of harmonic filter
CAUTION
Chiller Nameplate RLA
MUST
match chiller dataplate per compressor.
Figure 44: Settings View - Tower