INSTALLATION
Installation
Operating Limits
Table 1: Operating/Standby Limits
Acceptable Temperatures (WME-D)
1
R-515B
Condition
Component
Description
Min Temp
°F (°C)
Max Temp
°F (°C)
Standby
Evaporator
Water
35 (1.7)
140 (60)
Water w/ Antifreeze
2
35 (1.7)
140 (60)
Equipment Room
Air w/ Water in Vessels
4
34 (1.1)
140 (60)
Air w/ no Water in Vessels
4
-25 (-31.6)
140 (60)
Startup
Evaporator
Water
35 (1.7)
90 (32.2)
Water w/ Antifreeze
2
35 (1.7)
90 (32.2)
Condenser
Water
40 (4.4)
120 (48.9)
Equipment Room
Air
4,5
34 (1.1)
104 (40)
Operating
Evaporator
Entering Water
35 (1.7)
90 (32.2)
Leaving Water
3
35 (1.7)
70 (21.1)
Entering Water w/ Antifreeze
2
35 (1.7)
90 (32.2)
Leaving Water w/ Antifreeze
2
35 (1.7)
70 (21.1)
Condenser
Entering Water
40 (4.4)
120 (48.9)
Leaving Water
3
50 (10)
126 (52.2)
Equipment Room
Air
4,5
34 (1.1)
104 (40)
NOTES:
1
Contact a Daikin Applied representative for performance at specific operating conditions, as some limits depend on unit
configuration
2
Antifreeze temperature limits must have appropriate glycol concentration
3
Allowable leaving fluid temperatures depend on Saturation Temperature
4
5%-95% relative humidity, non-condensing
5
For non-conditioned equipment rooms please contact factory for maximum dew point, limits may depend on specific selection.