OPERATION
MAGNITUDE WME-D MAGNETIC BEARING CHILLER
DAIKIN APPLIED
44
Controller Inputs and Outputs
As outlined below, inputs and outputs vary between the unit
controller and the compressor controller.
Unit Controller Inputs and Outputs
The following tables list the unit controller inputs and outputs,
both analog and digital, as well as the stepper motor outputs.
Table 21: Unit Controller, Analog Inputs
Description
Wiring
Source
Signal
Sensor
Range
Entering
Evaporator
Water Tem-
perature
Chiller
NTC
Thermistor
10k @ 25°C
-40 to
125°C
Leaving Evap-
orator Water
Temperature
Chiller
NTC
Thermistor
10k @ 25°C
-40 to
125°C
Entering Con-
denser Water
Temperature
Chiller
NTC
Thermistor
10k @ 25°C
-40 to
125°C
Leaving Con-
denser Water
Temperature
Chiller
NTC
Thermistor
10k @ 25°C
-40 to
125°C
Liquid Line
Refrigerant
Temperature
Chiller
NTC
Thermistor
10k @ 25°C
-40 to
125°C
Evaporator
Refrigerant
Pressure
Chiller
Sealed
Gage
Transducer
0.5 to 4.5
VDC nom-
inal
0 to 100
psi
Liquid Line
Refrigerant
Pressure
Chiller
Sealed
Gage
Transducer
0.5 to 4.5
VDC nom-
inal
0 to 200
psi
Condenser
Refrigerant
Pressure
Chiller
Sealed
Gage
Transducer
0.5 to 4.5
VDC nom-
inal
0 to 200
psi
Reset of
Leaving Water
Temperature
Field
BAS
4 to 20 mA
Current
0 to
100%
Demand Limit
Field
BAS
4 to 20 mA
Current
0 to
100%
NOTICE
“Sensor Range” in
indicates the range of the input, NOT
the operating range of the chiller.
Table 22: Unit Controller, Digital Inputs
Description
Wiring
Signal
Source
States (Open/
Closed)
Front Panel
“Stop/Auto”
Switch
Chiller
Isolated
Switch Con-
tacts
Stop/Auto
Remote Start/
Stop
Field
Isolated
Switch or Re-
lay Contacts
Stop/Auto
Evaporator
Water Flow
Switch
Chiller & Field
(in series)
Isolated Flow
Switch Con-
tacts
No Flow/Flow
Condenser
Water Flow
Switch
Chiller & Field
(in series)
Isolated Flow
Switch Con-
tacts
No Flow/Flow
Table 23: Unit Controller, Analog Outputs
Description
Output Signal
Sensor Range
EXV Driver Signal
0 to 10 VDC
0 to 100% Open
Cooling Tower By-
pass Valve Position
0 to 10 VDC
0 to 100% Open
Cooling Tower VFD
Speed
0 to 10 VDC
0 to 100%
NOTICE
“Sensor Range” in
indicates the range of the output,
NOT the operating range of the chiller.
Table 24: Unit Controller, Digital Outputs
Description
Load
Rating
Alarm
Indicator Light
240 VAC
Evaporator Water
Pump #1
Pump Contactor
240 VAC
Evaporator Water
Pump #2
Pump Contactor
240 VAC
Condenser Water
Pump #1
Pump Contactor
240 VAC
Condenser Water
Pump #2
Pump Contactor
240 VAC
Cooling Tower Fan
#1
Fan Contactor
240 VAC
Cooling Tower Fan
#2
Fan Contactor
240 VAC
Содержание MAGNITUDE WME-D