www.DaikinApplied.com 47
IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
o
peraTIon
Events
Events do not generate a warning message to the operator but they may notify the BAS, if used. Chiller operation may be affected
by events.
Table 17:
Unit Events
Description
OITS Alarm Message
Alarm Reset
High Motor Current On Compressor #1
No Alert shown on OITS panel
No Alarm
High Motor Current On Compressor #2
No Alert shown on OITS panel
No Alarm
Evaporator Freeze Protect Comp 1
EVAP PUMP ON - Evaporator Pressure Low (Freeze)
Auto-clears
Evaporator Freeze Protect Comp 2
EVAP PUMP ON - Evaporator Pressure Low (Freeze)
Auto-clears
Evaporator Pump #1 Fault
No Alert shown on OITS panel
No Alarm
Evaporator Pump #2 Fault
No Alert shown on OITS panel
No Alarm
Re-Start Fault
No Alert shown on OITS panel
No Alarm
Re-Start Fault Circuit 1
No Alert shown on OITS panel
No Alarm
Re-Start Fault Circuit 2
No Alert shown on OITS panel
No Alarm
Table 18:
Compressor Events
Description
OITS Alarm Message
Alarm Reset
Bearing Fault 1
COMPR STOP - Compressor Fault
Auto-clears
Pauses 20 min after 3rd alarm in 50 min
Bearing Fault 2
COMPR STOP - Compressor Fault
Auto-clears
Pauses 20 min after 3rd alarm in 50 min
Motor Fault 1
COMPR STOP - Compressor Fault
Auto-clears
Pauses 20 min after 3rd alarm in 50 min
Motor Fault 2
COMPR STOP - Compressor Fault
Auto-clears
Pauses 20 min after 3rd alarm in 50 min
Drive Fault 1
COMPR STOP - Compressor Fault
Auto-clears
Drive Fault 2
COMPR STOP - Compressor Fault
Auto-clears
Internal Control Fault 1
COMPR STOP - Compressor Fault
Auto-clears
Internal Control Fault 2
COMPR STOP - Compressor Fault
Auto-clears
Содержание Magnitude WMC Series
Страница 4: ......
Страница 14: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 12 www DaikinApplied com Installation Figure 12 Wiring Index...
Страница 15: ...www DaikinApplied com 13 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation...
Страница 16: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 14 www DaikinApplied com Installation Figure 13 Controller Box Wiring...
Страница 19: ...www DaikinApplied com 17 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation...
Страница 67: ......