3 About the box
Installation manual
5
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728170-1 – 2023.03
DANGER
Tripping over loose wiring can tear it loose and cause
electrocution and fire.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may
cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure above.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
damage the head and make proper tightening
impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1 meter away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1 meter may NOT be sufficient.
NOTICE
ONLY applicable if the power supply is three‑phase, and
the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes ON and OFF
while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
2.3
Standards and regulations
Directives
Directive and
regulations
2006/42/CE
Harmonised standards EN 378-1:2016: Refrigerating systems and
heat pumps - Safety and environmental
requirements: Basic requirements,
definitions, classification and selection
criteria
EN 378-2:2016: Refrigerating systems and
heat pumps. Safety and environmental
requirements: Design, construction, testing,
marking and documentation
EN 60204-1:2018: Safety of machinery -
Electrical equipment of machines - Part 1,
General requirements
IEC 60335-2-89: Household and similar
electrical appliances - Safety - Part 2-89,
Particular requirements for commercial
refrigerating appliances and ice-makers
with an incorporated or remote refrigerant
unit or motor-compressor.
EN 12100 Risk assessment
Directive and
regulations
2006/42/CE
EN ISO 13857 :2020 Safety Distances
EN ISO 13854:2020 Minimum gaps
RED
EMC 2014/30/EU
Harmonised standards IEC 61000-6-8: Emission
IEC 61000-6-2: Immunity for Industrial
EN IEC 61000-3-2: ElectroMagnetic
Compatibility (EMC) Part 3-2, Limits - Limits
for harmonic current emissions (equipment
input current <= 16 A per phase)
EN IEC 61000-3-3: ElectroMagnetic
Compatibility (EMC) - Part 3: Limits -
Section 3, Limitation of voltage fluctuations
and flicker in low-voltage supply systems
for equipment with rated current ≤ 16 A
EN 301 489-1: ElectroMagnetic
Compatibility (EMC) standard for radio
equipment and services; Part 1, Common
technical requirements; Harmonised
Standard for ElectroMagnetic Compatibility
EN 301 489-17, ElectroMagnetic
Compatibility (EMC) standard for radio
equipment and services; Part 17, Specific
conditions for Broadband Data
Transmission Systems; Harmonised
Standard for ElectroMagnetic Compatibility
ETSI EN 300 328, Wideband transmission
systems; Data transmission equipment
operating in the 2,4 GHz band; Harmonised
Standard for access to radio spectrum
RoHS
RoHS 2011/65/EU
Harmonised standards
IEC EN 63000
Performance
EN 17432:2021 Packaged refrigerating units for walk-in cold rooms
- Classification, performance and energy consumption testing
Regulations
Regulation (EC) No
1907/2006
Registration, Evaluation, Authorisation and
Restriction of Chemicals (REACH)
3
About the box
▪ At delivery, the unit MUST be checked for damage and
completeness. Any damage or missing parts MUST be reported
immediately to the claims agent of the carrier.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
▪ Prepare in advance the path along which you want to bring the
unit to its final installation position.
▪ When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
▪ A forklift can be used for transport as long as the unit remains on
its pallet.