SiBE05-513A
Control Specification
Function and Control
43
3.12 Malfunctions
3.12.1
Sensor Malfunction Detection
Sensor malfunction may occur in the thermistor.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Fin thermistor
4. Outdoor air thermistor
3.12.2 Detection of
Overload
and
Over Current
Outline
In order to protect the inverter, detect an excessive output current, and for protecting
compressor, monitor the OL operation.
Detail
If the OL (compressor head) temperature exceeds 120°C (depending on the model),
the compressor gets interrupted.
If the inverter current exceeds 22 A, the compressor gets interrupted too.
3.12.3
Insufficient Gas Control
Outline
There are three ways of control to detect insufficient gas.
I Detecting by power consumption
If the power consumption is below the specified value and the frequency is higher than the
specified frequency, it is regarded as insufficient gas.
The power consumption is weak comparing with that in the normal operation when gas is
insufficient, and gas insufficiency is detected by checking a power consumption.
II Detecting by discharge pipe temperature
If the discharge temperature is higher than the target discharge pipe temperature, and the
electronic expansion valve is fully open (480 pulses) more than the specified time, it is regarded
as insufficient gas.
III Detecting by the difference of temperature
If the difference between inhale and exhale temperature is smaller than the specified value, it is
regarded as insufficient gas.
Frequency
Power consumption
Insufficient gas zone
55 Hz
(R2834)
Gas insufficient
zone
(R1391)
Содержание Inverter FLKS25BVMB
Страница 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Страница 14: ...SiBE05 513A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Cooling Only 6 1 2 Heat Pump 8 ...
Страница 19: ...Specifications SiBE05 513A 10 Specifications ...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE05 513A 16 Printed Circuit Board Connector Wiring Diagram ...
Страница 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Страница 83: ...Instruction SiBE05 513A 74 System Configuration ...
Страница 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Страница 153: ...Outdoor Unit SiBE05 513A 144 Removal Procedure When reassembling make sure to fit the hook Step Procedure Points ...
Страница 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Страница 168: ...SiBE05 513A Others 159 Part 8 Others 1 Others 160 1 1 Test Run from the Remote Controller 160 1 2 Jumper Settings 161 ...
Страница 171: ...Others SiBE05 513A 162 Others ...
Страница 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Страница 181: ...SiBE05 513A iv Index ...