Inspecting the Outdoor Unit
SiAUY361411EA
201
Parts Inspection
1.36 Inspecting the Heaters
Inspecting the oil separator heater
Measure the resistance between terminals.
Inspecting the accumulator heater
Measure the resistance between terminals.
Inspecting the oil return heater
Measure the resistance between terminals.
Measuring points
Measured value
Between terminals
570
Ω
±7%
Measuring points
Measured value
Between terminals
890
Ω
±10%
Measuring points
Measured value
Between terminals
5000
Ω
±7%