SiAUY361411EA
Inspecting the Outdoor Unit
Parts Inspection
198
1.33 Inspecting the Refrigerant System Sensors
Inspecting the high pressure switch
Check the continuity between terminals. There should be continuity while stopped.
Inspecting the pressure sensors
For each of the high and low refrigerant pressures, get the sensor value and actually measured
value by checking the refrigerant pressure with the outdoor unit's onboard checker and
measuring the refrigerant pressure with a manifold gauge. If the two values are approximately
equal, it means that the refrigerant pressure is normal.
[High pressure sensor]
You can convert the output voltage of the high pressure sensor into the equivalent pressure
using the table on
page 226
. The input voltage is 5 V (constant) when measured between the
main circuit board's CN4-2 (black) and -3 (red).
[Low pressure sensor]
You can convert the output voltage of the low pressure sensor into the equivalent pressure
using the table on
page 226
. The input voltage is 5 V (constant) when measured between the
main circuit board's CN4-5 (black) and -6 (red).
Inspecting the discharge temperature sensor
Measure the resistance between terminals. If the actually measured value is approximately
equal to the checker value, it means that the sensor is normal.
Inspecting the intake air temperature sensor
Measure the resistance between terminals. If the actually measured value is approximately
equal to the checker value, it means that the sensor is normal.
Inspecting the outdoor air temperature sensor
Measure the resistance between terminals. If the actually measured value is approximately
equal to the checker value, it means that the sensor is normal.
Inspecting the oil temperature sensor
Measure the resistance between terminals. If the actually measured value is approximately
equal to the checker value, it means that the sensor is normal.
Working pressure characteristics (factory default settings)
Type
Circuit open
Circuit closed
HPS1/2
4.0
MPa
3.15±0.15 MPa
High pressure sensor
Pressure range
0 to 4.15 MPa
Low pressure sensor
Pressure range
0 to 3.33 MPa
+0
-0.15
025958-00X
Connector
(red)
023465-00E
Connector
(white)
023466-00E
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...