SiAUY361411EA
Inspecting the Outdoor Unit
Parts Inspection
192
1.26 Inspecting the Outdoor Fan Motor
Caution
When you inspect the outdoor fan motor with the outdoor unit powered ON, take extreme care
not to directly touch the circuit board (except the switches) or you may get an electrical shock.
Even with the power OFF, there is a risk of an electric shock when any circuit board has an LED
still lit. Before accessing any circuit board, make sure that there is no circuit board whose
LED(s) are still lit.
Output voltage
∗
Reference value
1. Using a tester, check if the output voltage requirements specified above are met.
2. If the voltage is significantly different than specified above, stop the system using the
onboard checker and wait for 5 minutes; then, with the power shut OFF, check the harness
for continuity and the junction connectors for contact failure using a tester.
3. If the harness and connectors are OK, then check each component.
Inspecting the fan motor
Inspect the fan motor by measuring the resistance between its terminals.
∗
At 20°C (reference value)
Parts to inspect
Measuring points
During system stop
With actuator check ON
Power supply
circuit board
Between CN104-1 and -3
280 V DC
∗
280 V DC
∗
DCBL circuit
board
Between CN201-1 and -3
280 V DC
∗
280 V DC
∗
CN203
CN204
CN205
Between phases
0 V
∗
Speed (min
-1
)
Voltage
700
180±5 V AC
∗
600
180±5 V AC
∗
500
180±5 V AC
∗
Measuring points
Measured value (
Ω
)
∗
Power
supply
Between terminals #1(red) and #2 (white)
7.3±10%
Between terminals #1(red) and #3 (black)
7.3±10%
Between terminals #2(white) and #3 (black)
7.3±10%
Measuring points
Measured value (k
Ω
)
∗
Signal
Between #1 (pink) and #2 (gray)
100±10%
Between #1 (pink) and #3 (yellow)
10±10%
Between #1 (pink) and #4 (blue)
10±10%
Between #1 (pink) and #5 (amber)
10±10%
Between #2 (gray) and #3 (yellow)
100±10%
Between #2 (gray) and #4 (blue)
100±10%
Between #2 (gray) and #5 (amber)
100±10%
Between #3 (yellow) and #4 (blue)
20±10%
Between #3 (yellow) and #5 (amber)
20±10%
Between #4 (blue) and #5 (amber)
20±10%
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...