SiAUY361411EA
Inspecting the Outdoor Unit
Parts Inspection
190
1.24 Inspecting the Compressor Clutch
Output voltage
Inspecting the compressor clutch
Inspect the compressor clutch by measuring the resistance between its connectors and the
ground.
Parts to inspect
Measuring points
Actuator check
CH
ON
OFF
Compressor clutch 1 Between main circuit board's CN9-6 and ground (8)
05
12 V DC
0 V
Compressor clutch 2 Between main circuit board's CN9-7 and ground (8)
06
12 V DC
0 V
Type
Measuring points
Measured value
SD type (for GYEQ20AN)
Between
harnesses and
ground
3.2
Ω
MHI type (for GYEQ20AN/GYEQ30AN)
∗
Whether solenoid valves are used depends on the model.
Between
harnesses and
ground
6.3
Ω
025954-00X
025955-00X