SiAUY361411EA
Inspecting the Outdoor Unit
Parts Inspection
186
Inspecting the water motor-operated valve
Inspect the water motor-operated valve by measuring the resistance between its connectors.
1.18 Inspecting the Thermostat
Put the thermostat in a container filled with water. While heating the water with an electric
heater, measure the temperature and check when the valve begins opening and when it
becomes fully open.
∗
Because liquid packing is applied to the thermostat components before they are assembled,
do not reuse the components after disassembly. Use new thermostat components.
Measuring points
Measured value
Between terminals #2 (red) and #4 (pink)
70
Ω
Between terminals #1 (amber) and #2 (red)
70
Ω
Between terminals #2 (red) and #6 (yellow)
70
Ω
Between terminals #2 (red) and #3 (blue)
70
Ω
2
3
4
5
6
White
Brown
Blue
Blue
Orange
Orange
Pink
Red
(COM)
7 Yellow
Yellow
M
CN18
Yellow
-
Pink
Blue
Red Orange
MV
Blue
-
Brown
Yellow
Orange
Harness
028042-00E
Main circuit board
White
Thermostat
Begins opening
Fully open
60°C
60°C
75°C
71°C
71°C
85°C
023468-00E
Thermostat
71°C
Thermostat
60°C
023469-00E
Thermometer
Thermostat
Electric heater
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...