5
Indoor Unit
Installing The Mounting Plate
• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the
boring points on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting-plate retention spots and Dimensions
Use a tape measure
as shown.
Position the end of
t
Recommended mounting plate
retention spots fl spots in all)
Place a leveler
on these tabs.
the tape measure at I>
Applicable Unit Size*
t Recommende d mounUng p late
retentionspots(7spots1nall)
Liquid pipe and
Gas pipeend
Drainhose
position
Type
[H] X [W] X [D]
A
B
C
CD
298
X
800
X
229
800 116.5 116.5
0
298
X
821
X
235
821
128 126.5
®
298
X
885
X
229
885 116.5 116.5
©
298
X
906
X
235
906
127 127.5
* Unit size available on name plate.
Table No.4
Applicable Unit Size*
Type
I
[H] X [W] X [D]
®I
310
X
1100
X
239
* Unit size available on name plate.
Table No. 5
All dimensions are in mm.
Drilling A Wall Hole And Installing Wall Embedded Pipe
L'.t
WARNING----------------
For metal frame or metal board walls, be sure to use a wall embedded pipe and wall hole cover in the feed-through hole
to prevent possible heat, electrical shock, or fire.
1) Drill a feed-through hole with a 65mm
diameter through the wall at a
downward angle toward the outside.
2) Insert a wall embedded pipe into the hole.
3) Insert a wall hole cover into wall pipe.
Inside.......,... Outside
Wall embedded
pipe (field supply)
Wall hole cover
(field supply)
Содержание GTKC48UV16W
Страница 20: ......