
Field Setting from Remote Controller
ESIE15-13B
80
Field Setting
Graph 3
Target evaporating temperature control when "low humidity appli freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Change
thermostat
control
In order to increase continuous operation of the unit in low latent heat applications and avoid the
rise of temperature after thermostat OFF, the thermostat control will be changed when using
field settings 16(26)-2-03 & 16(26)-2-04.
Thermostat ON
Δ
Trs
≥
0.5 °C (No change from standard setting)
Thermostat OFF
Δ
Trs
≤
-2.0 °C for 5 minutes continuously.
Δ
Trs
≤
4.5 °C
2.8
Defrost Start Setting
Refer to “Defrost Operation” on page 48.
2.9
Slow start
Refer to “Slow start for EDP applications” on page 54.
Te target
(˚C)
Te target acceptable area
Remote controller setting temp.
Te target limited
≤
20˚C
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp.
>
setting
→
Te target down
Indoor temp.
<
setting
→
Te target up
Te target limited
≥
2˚C
(not to freeze)
Freeze protection
(40min. integrated coil temp.
≤
-1˚C)
Indoor Temp
(˚C DB)
Содержание GQI-Eco Series
Страница 2: ......
Страница 6: ...ESIE15 13B iv Table of Contents...
Страница 14: ...Introduction ESIE15 13B xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13B 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13B 94 Field Setting...