ESIE15-13B
Symptom-based Troubleshooting
Service Diagnosis
115
2.12 Swing Flap does not Operate
Applicable
Models
All models of SkyAir series
Method of Error
Detection
Visual check
Error Decision
Conditions
When ON/OFF of the micro-switch for positioning cannot be reversed even through the swing
flap motor for a specified amount of time (about 30 seconds).
Remark
Some functions can force the swing flap into a fixed position, although swing mode is selected
on the remote controller. This is not a unit error, but a control function to prevent draft to the
customer.
Before starting the troubleshooting, make sure the swing flap is not forced into such a fixed
position. (e.g. Hot start, defrost operation, thermostat OFF in heating operation or freeze
prevention in cooling operation. For details refer to "Swing Pattern Selection" on P.33.)
Supposed
Causes
Faulty swing motor
Faulty micro-switch
Faulty connector connection
Faulty indoor unit PCB