background image

6

CAUTION

To avoid possible personal injury, a safe, flat surface for 

service personnel should be provided.

WARNING

To prevent possible equipment damage, property damage, 

personal injury or death. The following bullet points must 

be observed when installing the unit.

 

Unit must be lifted by the four lifting holes located at the 

base frame corners. See Figure 4 - Rigging.

• 

  Lifting cables should be attached to the unit with 

shackles

• 

  The distance between the crane hook and the top of 

the unit must not be less than 60”.

• 

  Two spreader bars must span over the unit to prevent 

damage to the cabinet by the lift cables. Spreader 

bars must be of sufficient length so that cables do not 

come into contact with the unit during transport.

• 

  Remove wood struts mounted beneath unit base 

frame before setting unit on roof curb. These struts 

are intended to protect unit base frame from forklift 

damage. Removal is accomplished by extracting the 

sheet metal retainers and pulling the struts through 

the base of the unit. Refer to rigging label on the unit.

Refer to the Roof Curb Installation Instructions for proper 

curb installation. Curbing must be installed in compliance 

with the National Roofing Contractors Association Manual.

Rigging

Figure 4

CIRCULATING AIR AND FILTERS

Airflow Conversion

Units can easily be converted from horizontal to down 

discharge air flow delivery. See Figure 5A - Horizontal 

Flow Duct Cover Installation and Figure 5B - Downflow 

Duct Cover Installation. In down discharge or high static 

installations, the installer should measure the total external 

static and review the blower performance charts before 

performing the installation. In some installations it will be 

necessary to change the blower speed to provide proper 

air flow.

Horizontal Air Flow

Single phase models are shipped without horizontal duct 

covers. If needed, these kits may be ordered through 

Daikin’s Service Parts department.

REMOVE THESE COVERS

FOR HORIZONTAL DUCT

APPLICATIONS

Horizontal Flow Duct Cover Installation

Figure 5A

Down Discharge Applications

Cut insulation around bottom openings and remove panels 

from the bottom of the unit, saving the screws holding the 

panels in place.

Remove these panels

for downflow duct applications

Downflow Duct Cover Installation

Figure 5B

Ducting

Ducting work should be fabricated by the installing 

contractor in accordance with local codes. Industry 

manuals may be used as a guide when sizing and 

designing the duct system-such as NESCA (National 

Environmental Systems Contractors Association, 1501 

Wilson., Arlington, Virginia 22209).

The unit should be placed as close as possible to the 

space to be air-conditioned allowing clearance dimensions 

Содержание GPHM5 SEER2 M Series

Страница 1: ...ot bypass safety devices Affix this manual and Users Information Manual adjacent to the unit Daikin Comfort Technologies Manufacturing L P 19001 Kermier Rd Waller TX 77484 www goodmanmfg com 2022 Daik...

Страница 2: ...djustments 13 GPHM5 Thermostat Fan Only Mode 13 GPHM5 Humidity Control 13 SUPERHEAT AND SUBCOOLING 13 Refrigerant Charge Check 13 Checking Superheat 13 Checking Subcooling 14 Units with TXV Devices 14...

Страница 3: ...mance and or hazardous conditions may result from the use of such non devices WARNING HIGH VOLTAGE Disconnect all power before servicing or installing this unit Multiple power sources may be present F...

Страница 4: ...acilities and connections Location may be on any four sides of a home manufactured or modular to minimize noise Clearances and Accessibility The unit is designed to be located outside the building wit...

Страница 5: ...fficient structural support must be determined prior to locating and mounting the curb and package unit Curb insulation cant strips flashing and general roofing material are furnished by the contracto...

Страница 6: ...CULATING AIR AND FILTERS Airflow Conversion Units can easily be converted from horizontal to down discharge air flow delivery See Figure 5A Horizontal Flow Duct Cover Installation and Figure 5B Downfl...

Страница 7: ...OUND DUCT CONVERTER PANEL Manufactured Home Modification Kit Figure 6 It is strongly encouraged to use appropriately sized ducts based upon the CFM for your application unit s CFM If duct sizing throu...

Страница 8: ...te It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit The low voltage wiring must be connected between the unit control...

Страница 9: ...mate 60 second delay 6 Slowly lower the cooling temperature until the unit starts The compressor blower and fan should now be operating Allow the unit to run 10 minutes make sure cool air is being sup...

Страница 10: ...power to the compressor and outdoor fan motor 2 Crankcase Heater This item is ON whenever power is supplied to the unit and the crankcase heater thermostat is closed Crankcase heater thermostat close...

Страница 11: ...Figure 10 For Heat Pump units the expansion devices are Thermal Expansion Devices TXV and perform the same function on the heating cycle as on the cooling cycle The TXVs also act as check valves to al...

Страница 12: ...W2 C terminals on the board Should read 24 volts 8 If not as above replace control board 9 Set thermostat to off position and disconnect power Remove jumper from defrost thermostat and replace timer j...

Страница 13: ...cooling and T3 is medium speed heating T4 is high speed cooling and T5 is high speed heating To adjust the blower speed move the yellow and or white wires to T4 and T5 HEATING COOLING Speed Tap Defini...

Страница 14: ...eading 3 Check subcooling and superheat System should have a subcooling and superheat within the range listed on the Design Superheat and Subcooling table a If subcooling and superheat are low adjust...

Страница 15: ...g output It may also cause false defrosting Undercharge An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost accumulation on the...

Страница 16: ...ve contains refrigerant gases at certain temperatures 2 The discharge line should be the same temperature after the valves discharge line 3 The true suction should be the same as the suction line afte...

Страница 17: ...ce the compressor c Low voltage connection c At compressor terminals voltage must be within 10 of nameplate volts when unit is operating d Capacitor weak open or shorted d Check capacitor If defective...

Страница 18: ...7 1346 1305 1247 Watts 286 297 307 317 328 339 350 359 CFM 1775 1718 1673 1643 1588 1532 1482 1431 Watts 416 424 430 454 458 466 478 488 CFM 1271 1231 1186 1140 1094 1041 986 915 Watts 169 181 190 201...

Страница 19: ...38 143 CFM 1416 1377 1339 1294 1249 1198 1143 1085 Watts 267 277 288 296 302 311 318 325 CFM 1508 1466 1417 1380 1330 1282 1242 1199 Watts 406 412 418 435 437 434 455 465 CFM 1142 1092 1047 1009 965 9...

Страница 20: ...34 51 47 SUPPLY 1 3 8 A RETURN POWER WIRE ENTRANCE 4 1 8 2 1 8 6 16 16 5 B B CONTROL WIRE ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 18 7 8 3 8 2 34 51 47 SUPPLY A RETURN 16 5 B CONTROL WIRE...

Страница 21: ...R CONDUCTOR ONLY 2 TO CHANGE EVAPORATOR MOTOR SPEED MOVE YELLOW AND WHITE LEADS FROM EM 2 AND 3 TO 4 AND 5 IF BOTH LEADS ARE ENERGIZED THE HIGHER SPEED SETTING IS USED 3 FOR 208 VOLT TRANSFORMER OPERA...

Страница 22: ...inum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This cl...

Страница 23: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Страница 24: ...itles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminish their warranty rights The duration of warranty coverages...

Отзывы: