SiE 00-07
Troubleshooting (Inverter)
Troubleshooting R-407C PLUS Series
165
5.7
Outdoor Unit: Inverter Over-Ripple Protection
Remote Controller
Display
P1
Supposed Causes
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter unit
Defect of K1M
Improper main circuit wiring
Troubleshooting
(VF069)
Is
the voltage
imbalance applied to the
inverter in excess of 20 V
(Y1)?
∗
2
NO
Part or wiring defect
After turning the power supply
OFF, check and repair the main
circuit wiring or parts.
(1) Loose or disconnected wiring
between power supply and
inverter
(2) KIM contact disposition, fusion
or contact is poor.
(3) Loose or disconnected noise
filter
Using a device capable of
constant recording of power
supply voltage record power
supply voltage between 3
phases (L1 ~ L2, L2 ~ L3,
L3~L1) for about one continuous
week.
Open phase
Normalize field cause.
Power supply voltage imbalance
Explanation for users
Fix power supply voltage
imbalance.
YES
YES
NO
Imbalance
in supplied voltage is
in excess of 20 V (Y1).
∗
1
Open phase?
<When voltage monitoring is possible:>
∗
1. Measure voltage at the X1M power supply terminal
block.
∗
2. Measure voltage at terminals L1, L2 and L3 of the diode
module inside the inverter while the compressor is
running.
∗
In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results"and leave it up to
him to improve the imbalance.
Be sure to explain to the user that there
is a "power supply imbalance" for
which DAIKIN is not responsible.
Disposal
YES
NO
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...