Troubleshooting (Inverter)
SiE 00-07
162
Troubleshooting R-407C PLUS Series
5.4
Outdoor Unit: Inverter Stall Prevention, Compressor Lock
Remote Controller
Display
L9
Supposed Causes
Defect of compressor
Pressure differential start
Defect of inverter unit
Troubleshooting
Inverter
output voltage
check
Inverter output
voltage is not balanced.
(Normal if within
±
8V)
(Note) Must be
measured when
frequency
is stable.
Unsatisfactory pressure equalization
Check refrigerant system.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration and
operating status of the compressor.
YES
Replace the inverter unit.
NO
NO
Reset and restart.
NO
The difference
between high and low
pressure when starting is 2
kg / cm
2
= (0.196
MPa).
YES
YES
Disconnect the connection
between the compressor and
inverter.
After turning
on again, "L9" blinks
again.
(VF066)