SiE 00-07
Troubleshooting
Troubleshooting R-407C PLUS Series
149
3.27
Malfunction of Transmission Between Indoor Units
Remote Controller
Display
U4
Supposed Causes
Indoor to outdoor,outdoor to outdoor crossover wiring disconnection, short circuit or wrong check
Outdoor unit power supply is OFF
System address doesn’t match
Defect of indoor unit PC board
Defect of outdoor unit PC board
Troubleshooting
(VF054)
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
Supply 220~240 V.
Replace the fuse.
Fix the indoor/outdoor unit
transmission wiring.
Replace the outdoor unit PC
Board (A1P).
YES
NO
YES
Replace the indoor unit PC Board.
Push and hold the RESET button
on the outdoor unit PC Board for
5 seconds.
Fix the indoor/outdoor unit
transmission wiring.
YES
NO
NO
YES
Has
the indoor or
outdoor unit PC
board been replaced,
or has the indoor - outdoor or
outdoor - outdoor unit
transmission wiring
been modified?
All
indoor unit
remote controllers of the same
refrigerant system
display "U4."
NO
Outdoor unit PC
board microcomputer monitor
(HAP) blinks.
NO
NO
Operation
ready lamp (H2P) is
blinking.
Is indoor
- outdoor and outdoor -
outdoor unit transmission
wiring normal?
YES
The fuse on
the outdoor unit's PC board
is burnt.
Replace the transformer.
replacement
Replace outdoor unit PC board.
(A1P)
NO
The secondary
voltage of the transformer is
about 30 V.
NO
The voltage
between terminals R
and S of the outdoor unit PC
board is 220~240 V
(60Hz) or 220 V
(50 Hz).
∗
The unit will not operate for
up to 12 minutes.
Reset the power supply.
YES
YES
YES
NO
YES
Wait to lamp goes off.
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...