SiE 00-07
Troubleshooting
Troubleshooting R-407C PLUS Series
139
3.17
Outdoor Unit: Malfunction of Moving Part of Electronic Expansion Valve (Y1E)
Remote Controller
Display
E9
Supposed Causes
Defect of moving part of electronic expansion valve
Defect of outdoor unit PC board (A1P)
Defect of connecting cable
Troubleshooting
∗
1 Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between the
connector pins.
(Normal)
: Continuity Approx. 300
Ω
: Continuity Approx. 150
Ω
×
: No continuity
(VF043)
Electronic
expansion valve is
connected to X12A of outdoor
unit PC board
(A1P).
Normal
when coil check (
∗
1)
of the moving part of the
electronic expansion
valve is checked.
The connecting cable
is short-circuited or
disconnected.
Replace the connecting cable.
Replace outdoor unit PC board A1P.
NO
NO
NO
Replace the moving part of the
electronic expansion valve.
After connecting, turn the power off and
then back on again.
YES
YES
YES
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
×
×
2. Yellow
×
×
3. Orange
×
×
4. Blue
×
5. Red
×
6. Brown
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...