20 Configuration
20.1 Field setting
Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
▪
Ceiling height
▪
Decoration panel type
▪
Air flow direction range
▪
Air volume when thermostat control is OFF
▪
Time to clean air filter
▪
Thermostat sensor selection
▪
Thermostat differential changeover (if remote sensor is used)
▪
Differential automatic changeover
▪
Auto-restart after power failure
▪
Function for refrigerant leak detection
INFORMATION
▪
The connection of optional accessories to the indoor unit might cause changes to
some field settings. For more information, see the installation manual of the
optional accessory.
▪
Following setting are only applicable when using the BRC1H52* user interface.
When using any other user interface, see the installation manual or service
manual of the user interface.
Setting: Ceiling height
This setting must correspond with the actual distance to the floor, capacity class
and air flow directions.
▪
For 3-way and 4-way airflows (which require an optional blocking pad kit), see
the installation manual of the optional blocking pad kit.
▪
For all-round airflow, use the table below.
If the distance to the floor is (m)
Then
(1)
FXFN50
FXFN71, FXFN112
M
SW/C1
—/C2
≤2.7
≤3.2
13 (23)
0
01
2.7<x≤3.0
3.2<x≤3.6
02
3.0<x≤3.5
3.6<x≤4.2
03
Setting: Decoration panel type
When installing or changing the decoration panel type, ALWAYS check if the
correct values are set.
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number /
C1
: First code number
•
—: Value number /
C2
: Second code number
•
: Default