4 Preparation

Installation manual

7

FWE03~11D
Fan coil units
3P443944-5P – 2021.12

3.2.1

Identification label: Fan coil unit

Location

Model identification

Example: 

FW E 03 D A F N 5 V3 — L

Code

Description

FW

Water fan coil unit

E

Flex Low Static Pressure (LSP) without casing

03

Capacity class: 03=1.5 kW

D

Major model change (A to Z)

A

Minor change

F

F: 4 pipe

T: 2 pipe

N

N: Without valve

V:3 way ON/OFF 230 V valve

T:2 way ON/OFF 230 V valve

5

Hendek factory

V3

Fan motor / single phase / 50 Hz / 220~240 V

-

No option

Code

Description

L

S: Left side water – Left side electric connection

L: Left side water – Right side electric connection

T: Right side water – Right side electric connection

R: Right side water – Left side electric connection

4

Preparation

4.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.

It contains information about:

▪ Preparing the installation site

▪ Preparing the water piping

▪ Preparing the electrical wiring

4.2

Preparing the installation site

WARNING

Do NOT place objects below the fan unit that may get wet.
Otherwise  condensation  on  the  main  unit  or  water  pipes,
air filter dirt or drain blockage may cause dripping, resulting
in fouling or failure of the object concerned.

NOTICE

Please consult with your dealer to ensure that the external
static pressure of the unit is not exceeded.

INFORMATION

The sound pressure level is less than 70 dBA.

CAUTION

Do not use suspension bolts in case of vertical installation.
Vertical  installation  must  be  performed  with  the  vertical
installation kit (ESFH01D5 ,ESFH02D5 ,ESFH03D5 ).

INFORMATION

The  spacing  between  ceiling  and  unit  should  be  ≥10  mm
and the suction space should be ≥150 mm.

Do not install or operate the unit in rooms mentioned below.

▪ Places  with  mineral  oil,  or  filled  with  oil  vapour  or  spray,  like  in

kitchens (plastic parts may deteriorate).

▪ Where  corrosive  gas  like  sulphurous  gas  exists.  Copper  tubing

and brazed spots may corrode.

▪ Where  the  air  contains  high  levels  of  salt,  such  as  that  near  the

coast and where voltage fluctuates a lot (e.g. in factories). Also in
vehicles or vessels.

▪ In  places  where  there  is  machinery  that  emits  electromagnetic

waves.  Electromagnetic  waves  may  disturb  the  control  system,
and cause malfunction of the equipment.

▪ In  places  where  there  is  a  risk  of  fire  due  to  the  leakage  of

flammable  gases  (example:  thinner  or  gasoline),  carbon  fibre,
ignitable dust.

Select an installation site where the following conditions are fulfilled
and that meets your customer approval.

The  space  around  the  unit  is  adequate  for  maintenance  and
servicing.  The  space  around  the  unit  allows  sufficient  air  circulation
and air distribution see space required for installation.

Содержание FWE03D Series

Страница 1: ...Installation manual Fan coil units English Installation manual Fan coil units FWE03D FWE04D FWE05D FWE06D FWE07D FWE08D FWE10D FWE11D ...

Страница 2: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Страница 3: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Страница 4: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Страница 5: ...or trained users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of Fan coil unit installation manual Installation instructions Format Paper in the box of the fan coil unit Latest revisions of the supplied documentation may be available on the regional Daikin website ...

Страница 6: ...eck if the installation location can support the unit s weight Poor installation is hazardous It can also cause vibrations or unusual operating noise Provide sufficient service space Do NOT install the unit so that it is in contact with a ceiling or a wall as this may cause vibrations DANGER RISK OF ELECTROCUTION Do NOT operate the fan coil units with wet hands An electrical shock may result DANGE...

Страница 7: ...e consult with your dealer to ensure that the external static pressure of the unit is not exceeded INFORMATION The sound pressure level is less than 70 dBA CAUTION Do not use suspension bolts in case of vertical installation Vertical installation must be performed with the vertical installation kit ESFH01D5 ESFH02D5 ESFH03D5 INFORMATION The spacing between ceiling and unit should be 10 mm and the ...

Страница 8: ...he unit must be installed 2 5 m from the floor where the unit is hanging in the ceiling 150 mm High floor standing type 10 mm Floor standing type Vertical filter maintenance space should be considered as indicated 150 10 mm Wall mounted type bottom suction 10 150 mm Wall mounted type front suction 10 10 mm ...

Страница 9: ... or telephone earth Incomplete earthing may cause electrical shock Make sure to install the required fuses or circuit breakers Make sure to install an earth leakage protector Failure to do so may cause electrical shock or fire NOTICE The equipment described in this manual may cause electronic noise generated from radio frequency energy The equipment complies to specifications that are designed to ...

Страница 10: ...r bracket to the suspension bolt Fix the unit securely a b c d a Nut field supply b Washer field supply c Hanger bracket d Double nut field supply 4 Adjust the unit to the correct position for installation 1 100 5 Check if the unit is horizontally levelled Do not install the unit tilted If the unit is tilted against the direction of the condensate flow drain piping side raised it will cause water ...

Страница 11: ...ers with a water level a or a water filled plastic tube b b a Floor standing type ESFH01D5 In case of floor standing installation please follow the instruction as shown below 1 Remove the air filter 2 Remove the service cover c and air filter a from the unit a c 3 Insert the rubber support b included in the option kit in the free area between the side plate and the bottom flanges 4 Reattach the re...

Страница 12: ... it to the floor using screws f in the installation leg holes f d f Screw field supply 9 Adjust the unit to the correct position for installing 1 100 10 Check if the unit is horizontally levelled Do NOT install the unit tilted If the unit is tilted against the direction of the condensate flow drain piping side raised it will cause water to drip Check if the unit is levelled at all four corners wit...

Страница 13: ...om or front suction in the wall mounted type Please follow the instruction in case of wall mounting installation as shown below 1 Drill the holes on the wall according to the dimensions as shown on the table below a b c Model a mm b mm c mm FWE03 05D 485 50 710 FWE06D 910 FWE07 11D 1110 2 Mount the wall hangers on the wall with using the dowels a and screws b d 10 mm a ...

Страница 14: ...cause the unit to malfunction CAUTION Valves should always be used to control the water circulation in the unit The valve should be of the NC normally closed type so that the valves are closed when the unit is not operating This will prevent condensate water from being produced 5 2 1 To connect the water piping 1 Connect the water inlet and outlet connections of the fan coil unit to the water pipi...

Страница 15: ...ditional filling with water afterwards may be required To purge the system use the special function as described in 6 Commissioning 423 NOTICE Make sure water quality complies with EU directive 2020 2184 5 2 3 Installation of the valve kits NOTICE Make the wiring according to the wiring diagram of the remote controller INFORMATION Below graphics show 4 pipe models 2 pipe models are connected in th...

Страница 16: ...a b 3 Connect the actuator c to the valve body c 4 Wrap the thermal insulation d in the kit to prevent condensation and heat loss d 5 The kit is ready for main pipes connection The threads e connected to the main pipes of the valve body are DN20 Since no connection is made to the water outlet lines water out threads are 3 4ʺ female BSP ...

Страница 17: ...se The difference should be taken into account when preparing the installation area 5 mm a b 5 mm a b Model Option kit Kvs value m3 h diverter mixing Max operation pressure PN bar Actuator power supply 2 pipe 3 way E3V2VN02V3WA 2 8 2 5 16 1 Ph 230 V 50 60 Hz NC Normally closed 4 pipe 3 way E3V4VN02V3WA 1 Wrap teflon tape field supply on the end of the water pipes a and connect it to the water inle...

Страница 18: ...2 a 2 Connect the 3 way valve body b to the water pipes a b 3 Connect the actuator c to the valve body c 4 Wrap the thermal insulation d in the kit to prevent condensation and heat loss d 5 The kit is ready for main pipes connection The threads e connected to the valve body are DN20 ...

Страница 19: ...V3DA E4V4PN10V3DA 1 1 Wrap teflon tape field supply on the end of the nipple c and water pipe d then connect it to the water inlet and outler line Then connect the connection pipe a by placing a gasket b between it and nipple c d a b c 2 Connect the proportional valve body e by placing the gasket b in between b e 3 Connect the actuator f to the valve body f 4 Wrap the thermal insulation g in the k...

Страница 20: ...ss in the connection may deteriorate the protection Use the specified electric wire refer to Specifications for field wiring 49 Connect the wire securely to the terminal Use the appropriate tightening torque N m Power supply terminal block tightening torque 1 44 1 88 N m Keep the wiring neat so that wires do NOT obstruct other equipment or force the terminal cover to pop open Make sure the cover c...

Страница 21: ...e side in the field NOTICE When attaching the terminal cover make sure not to pinch any wires 1 Remove the terminal cover terminal cable holder earth wire and fan motor cables a Terminal cover b Wiring diagram label c Power supply cable d Terminal strip e Earth wire f Cable holder 2 Release the fan motor cable from the cable holders a a Fan motor cable 3 Change the direction of the fan motor cable...

Страница 22: ... t o t h e n a m e p l a t e L N C 1 Q 1 M M G R N Y L W F 1 U X 1 M 1 5 G R N R E D O R G B R N Y L W B L U G R E E N R E D O R A N G E B R O W N Y E L L O W B L U E N O T E G R N R E D O R G B R N Y L W B L U C 1 G R N Y L W F A N S P E E D S W I T C H X 1 M 2 1 3 4 5 L N L N F 1 U G R N Y L W G R N Y L W M 1 Q 1 M 6 Connect the power supply and remote controller cables to the terminal 7 Attach ...

Страница 23: ...rth wires have been connected properly and that the earth terminals are tightened Fuses circuit breakers or protection devices Check that the fuses circuit breakers or the locally installed protection devices are of the size and type specified in 4 4 Preparing electrical wiring 49 Be sure that neither a fuse nor a protection device has been bypassed Internal wiring Visually check the electrical co...

Страница 24: ...1 Switch off the power supply 2 The air filter can be installed in 1 of 2 locations on this product side and bottom Remove the filter by sliding as shown below Horizontal installation Remove the filter by sliding min 200 mm Vertical installation Push the tabs at the filter and pull it back min 70 mm ...

Страница 25: ...il units 3P443944 5P 2021 12 High floor standing Pull the filter and remove from the unit 3 Use a vacuum cleaner or wash air filter with water When the air filter is very dirty use a soft brush and neutral detergent 4 Set the air filter back to its original position ...

Страница 26: ...instruction list Materials Item Electrical part fan motor capacitor 1 Aluminium fin copper tube galvanized steel plate brass 10 Plastic 2 18 8 22 27 Plastic metal 3 17 24 Plastic frame plastic net 4 Galvanized steel 5 9 13 14 16 20 23 25 26 Galvanized steel plastic foam 6 7 11 12 15 19 Plastic foam 21 9 Technical data A subset of the latest technical data is available on the regional Daikin websit...

Страница 27: ... 505 56 42 A B C D mm Units mm A B C D FWE03 05D 719 757 799 909 FWE06D 919 957 999 1109 FWE07 11D 1119 1157 1199 1309 Vertical outlook High floor standing type 136 220 711 561 501 418 404 79 129 112 175 206a mm a In case of high floor standing kit ESFH03D5 usage Floor standing outlook ...

Страница 28: ...747 909 FWE06 919 957 947 1109 FWE07 11D 1119 1157 1147 1309 Additional drain pan ESFD01D6 CAUTION Make sure to attach the drain socket rubber after installing the additional drain pan Otherwise condensation on the main unit or water pipes air filter dirt or drain blockage may cause dripping resulting in fouling or failure of the object concerned Horizontal installation b c a a Additional drain pa...

Страница 29: ...9 Technical data Installation manual 29 FWE03 11D Fan coil units 3P443944 5P 2021 12 Vertical installation c b a a Additional drain pan b Drain socket rubber c Drain socket ...

Страница 30: ... 9 3 Wiring diagram On terminal English Translation Connection X1M Main terminal Field supply Protective earth Earth Field wire Fan motor cable WHT White GRN Green RED Red ORG Orange BRN Brown YLW Yellow BLU Blue GRN YLW Green yellow C1 Capacitor F1U Fuse X1M Terminal strip M Fan motor ...

Страница 31: ......

Страница 32: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P443944 5P 2021 12 Copyright 2019 Daikin Verantwortung für Energie und Umwelt ...

Отзывы: