5 Installation
Installation manual
14
FWE03~11D
Fan coil units
3P443944-5P – 2021.12
b
b
b
b
3
Hang the unit from the hangers and make sure that the hangers
are engaged correctly as shown at picture below.
4
Do NOT install the unit tilted. If the unit is tilted against the
direction of the condensate flow (drain piping side raised), it will
cause water to drip.
5
Please check, if the unit is levelled with a water level (a) or a
water filled plastic tube (b).
a
b
5.2
Connecting water piping
NOTICE
Do not use excessive force when connecting the piping.
This could deform the unit piping. Deformation of the piping
can cause the unit to malfunction.
CAUTION
Valves should always be used to control the water
circulation in the unit. The valve should be of the NC
(normally closed) type so that the valves are closed when
the unit is not operating. This will prevent condensate
water from being produced.
5.2.1
To connect the water piping
1
Connect the water inlet and outlet connections of the fan coil
unit to the water piping.
b
d
c
a
f
e
a
Chilled water inlet (3/4” female BSP)
b
Chilled water out (3/4” female BSP)
c
Heating water inlet (3/4” female BSP)
d
Heating water out (3/4” female BSP)
e
Drain pipe connection (Ø17 mm male no thread)
f
Air purge valve
Remark:
Use a 3/4" male BSP pipe in case of direct connection to
the unit.
2
The complete water circuit, including all piping, must be
insulated to prevent condensation and reduced capacity.