Installation manual
11
FWC
Fan coil units
4PW64525-1B – 2014.03
Commission the fan coil unit
5.2.
Configure the unit
It is important that all information in this chapter is read sequentially by
the installer and that the unit is configured as applicable.
Configuration of the unit is done trough the controller in accordance
with the installation condition.
Q
Setting can be made by changing the “Mode No.”, “First code
No.” and “Second code No.”.
Q
For setting and operation, refer to “Field setting” in the installation
manual of the controller.
Setting ceiling height
Adjust the Second code No. according to the table below so that it
corresponds to the ceiling height of your installation. (Second code
No. is factory set to “01”)
Table 5.2: Ceiling height setting
Setting air discharge direction
For changing air discharge direction (2, 3 or 4 directions), refer to the
option handbook of the optional blocking pad kit. (Second code No. is
factory set to “01” for all-round air discharge)
Setting air filter sign
Remote controllers are equipped with liquid crystal air filter signs to
display the time to clean the air filter. Change the Second code No.
Depending on the amount of dirt or dust in the room. (Second code
No. is factory set to “01” for air filter contamination-light)
Table 5.3: Air filter contamination
When using wireless remote controllers it is necessary to use address
setting. Refer to the controller installation manual for the setting
instructions.
Activating forced OFF and ON/OFF operation
The following table explains “forced OFF” and “ON/OFF operations” in
response to the input signal.
Table 5.4: Forced OFF and ON/OFF operation
1
Turn the power on and then use the remote controller to select
operation.
2
Set the remote controller to the field set mode.
Table 5.5: Forced OFF and ON/OFF selection
Commission the fan coil unit
5.3.
Test the installation
After installation, the installer is obliged to verify correct operation.
In case something is wrong with the unit and it does not operate,
contact your local DAIKIN dealer.
Test operation before installing decoration panel
1
Open the water inlet valve(s).
2
Open the water outlet valve(s).
3
Set to cooling operation with the remote controller and start
operation by pushing
ON/OFF
button.
4
Press
Inspection/Test Operation
button
4 times and
operate at
Test Operation
mode for 3 minutes.
5
Press
Inspection/Test Operation
button
and operate
normally.
6
Confirm function of unit according to the operation manual.
7
Turn off the main power supply after operation.
Test operation after installing decoration panel
1
Open the water inlet valve(s).
2
Open the water outlet valve(s).
3
Set to cooling operation with the remote controller and start
operation by pushing
ON/OFF
button.
4
Press
Inspection/Test Operation
button
4 times (2
times for wireless remote controller) and operate at
Test Opera-
tion
mode for 3 minutes.
5
Push
air flow direction adjust
button
to make sure
the unit is in operation.
6
Press
Inspection/Test Operation
button
and operate
normally.
7
Confirm function of unit according to the operation manual.
Commission the fan coil unit
5.4.
Handover to the user
Once the test run is finished and the unit operates properly, fill in the
sheet “Handover of the installation to the user” which is an annex of
the user manual.
Service and maintenance
Service and maintenance
Ceiling height
(m)
Mode No.
First code No.
Second code
No.
≤
3.2
13(23)
0
01
>3.2 or
≤
3.6
13(23)
0
02
>3.6 or
≤
4.2
13(23)
0
03
Setting
Display
interval
Mode No.
First code
No.
Second
code No.
Light
±2500 hrs
10(20)
0
01
Heavy
±1250 hrs
10(20)
0
02
No display
—
10(20)
3
02
Forced OFF
ON/OFF operations Protective
equipment input
Input “ON” stops
operation
Input OFF
→
ON:
turns on the unit
(impossible by
remote controllers)
Input ON: enables
abnormal system
stop (an error code
will be displayed)
Input “OFF” enables
control
Input ON
→
OFF:
turns off the unit (by
remote controller)
Input OFF: enables
normal operation
Setting
Mode No.
First code
No.
Second
code No.
Forced OFF
12(22)
8
01
ON/OFF
operation
12(22)
8
02
Protective
equipment
input
12(22)
8
03
Information
When using a wireless remote controller, conduct a test
operation after installing the decoration panel.
Danger: electric shock
“Precautions for installation” on page 2
.