English
1-3
The indoor unit must be installed such that there is no short
circuit of the cool discharge. Respect the installation clearance.
Do not put the indoor unit where there is direct sunlight on
unit. The location is suitable for piping and drainage and it
must have a large distance between a door and unit.
In cases where the temperature above the ceiling might
reach 30°C or the humidity RH80%, reinforce the drain pan
insulation (10mm or thicker) or adding secondary Drain
Pan. Condensation may form on the surface of the insulating
material.
Provide clearance for servicing ease and optimal air flow as
shown in the diagram.
INSTALLATION OF THE INDOOR UNIT
!
CAUTION
Do not install the unit at altitude over 2000m for both indoor and outdoor.
300mm* or more
300mm
or more
10mm
* Can be smaller than 300mm if ceiling is removable.
Floor
2300mm or more
Ceiling
Insulation material
(field supply)
Aluminium tape
(field supply)
Air outlet side
Air inlet side
See Detail A
Field supply
Washer for hanger bracket
(attached)
Tighten
Detail A
Aluminium tape
(field supply)
Ceiling Concealed Drain Piping Work
The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and
condensation.
For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
Ensure the drain pipe is securely insulated.
Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
In humid environments, use an extra drain pan to cover the entire area of the indoor unit.
•
•
•
•
•
•
DRAIN PIPE
The suggested slope of the
drain pipe is at least 1:50
Insulate securely
10mm (0.39")
Ceiling Concealed Mounting
Use the hanger supplied with the unit.
Make sure that the ceiling is sufficiently strong to withstand
the weight.
•
•
1 IM-CCFWD-0915(1)-DAIKIN-EN.ind3 3
1 IM-CCFWD-0915(1)-DAIKIN-EN.ind3 3
4/14/16 5:49:22 PM
4/14/16 5:49:22 PM