The indoor unit must be installed such that there is no short 
circuit of the cool discharge. Respect the installation clearance. 
Do not put the indoor unit where there is direct sunlight on 
unit. The location is suitable for piping and drainage and it 
must have a large distance between a door and unit.

In cases where the temperature above the ceiling might 
reach 30°C or the humidity RH80%, reinforce the drain pan 
insulation (10mm or thicker) or adding secondary Drain 
Pan. Condensation may form on the surface of the insulating 
material.

Provide clearance for servicing ease and optimal air flow as 
shown in the diagram.

INSTALLATION OF THE INDOOR UNIT

!

 

CAUTION

Do not install the unit at altitude over 2000m for both indoor and outdoor.

300mm* or more

300mm 

or more

10mm 

* Can be smaller than 300mm if ceiling is removable.

Floor

2300mm or more

Ceiling

Insulation material
(field supply)

Aluminium tape 
(field supply)

Air outlet side

Air inlet side

See Detail A

Field supply

Washer for hanger bracket 
(attached)

Tighten

Detail A

Aluminium tape 
(field supply)

Ceiling Concealed Drain Piping Work

The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and 
condensation. 
For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
Ensure the drain pipe is securely insulated.
Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
In humid environments, use an extra drain pan to cover the entire area of the indoor unit.





DRAIN PIPE
The suggested slope of the 
drain pipe is at least 1:50

Insulate securely

10mm (0.39")

Ceiling Concealed Mounting

Use the hanger supplied with the unit.
Make sure that the ceiling is sufficiently strong to withstand 
the weight.


1 IM-CCFWD-0915(1)-DAIKIN-EN.ind3   3

1 IM-CCFWD-0915(1)-DAIKIN-EN.ind3   3

4/14/16   5:49:22 PM

4/14/16   5:49:22 PM

Содержание FWC02FD

Страница 1: ...IM CCFWD 0915 1 DAIKIN Part Number R08019044145A Installation Manual Chilled Water Fan Coil Unit English MODELS FWC02FD FWC03FD FWC04FD FWC05FD FWC06FD FWC08FD FWC10FD CVR IM CCFWD 0915 1 DAIKIN EN i1...

Страница 2: ...CVR IM CCFWD 0915 1 DAIKIN EN i2 2 CVR IM CCFWD 0915 1 DAIKIN EN i2 2 4 13 16 3 33 42 PM 4 13 16 3 33 42 PM...

Страница 3: ...KA 32 20 552 129 20 11 143 87 71 247 186 31 KE KD KC KB KA 31 321 183 48 31 140 32 552 11 186 87 71 31 247 20 20 129 143 Dimension Model KA KB KC KD KE FWC02 03FD 619 477 437 440 501 FWC04 05FD 870 72...

Страница 4: ...or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen keep flour away from going into suction of the unit This unit is not suitable forfactory used where cuttin...

Страница 5: ...ield supply Air outlet side Air inlet side See Detail A Field supply Washer for hanger bracket attached Tighten Detail A Aluminium tape field supply Ceiling Concealed Drain Piping Work The drain pipe...

Страница 6: ...Do not use contaminated or damaged pipe and fitting for installation Some main fitting components are needed in the system to enhance the capacity and ease of service such as gate valve balancing val...

Страница 7: ...l Indoor FWC02FD FWC03FD FWC04FD FWC05FD Voltage Range Indoor 220V 240V 50Hz Power Supply Cable Size mm2 Number of Conductors 1 5 5 1 5 5 1 5 5 1 5 5 Recommended Time Delay Fuse A 1 1 1 1 Model Indoor...

Страница 8: ...ressure 16 bar Air temperature as below Cooling Mode OPERATING RANGE Temperature Ts C F Th C F Minimum indoor temperature 19 0 66 2 14 0 57 2 Maximum indoor temperature 32 0 89 6 23 0 73 4 OVERALL CHE...

Страница 9: ...air filter to the end of air filter rail Put back the side air filter cover Figure 2 Remove air filter to bottom Figure 3 Remove bottom air filter cover Slide and pull down air filter from air filter...

Страница 10: ...etting and operate the unit at high fan speed Water flowing out from the air conditioner unit 5 Switch off unit and call local dealer serviceman If the fault persists please call your local dealer ser...

Страница 11: ...CVR IM CCFWD 0915 1 DAIKIN EN i3 3 CVR IM CCFWD 0915 1 DAIKIN EN i3 3 4 13 16 3 33 42 PM 4 13 16 3 33 42 PM...

Страница 12: ...Importer for Turkey Allianz Plaza Kucukbakkalkoy Mah Kay sdagi Cad No 1 34750 Atasehir ISTANBUL TURKIYE In the event that there is any conflict in the interpretation of this manual and any translatio...

Отзывы: