SiBE01-829
Control Specification
Functions and Control
25
3.5
Heating
Peak-cut Control
Outline
During heating operation, heating peak-cut control is activated according to the temperature of
the indoor heat exchanger to prevent abnormal high pressure.
Detail
Conditions for starting
Temperature of the indoor heat exchanger
>
68°C.
While controlling
The compressor halts.
The outdoor fan switches ON/OFF according to the temperature of the indoor heat
exchanger.
Conditions for ending
Temperature of the indoor heat exchanger < 50°C (only for the first time)
or
Reset manually by pressing ON/OFF button (for the second time).
(R8497)
OFF
OFF
ON
ON
50˚C
55˚C
68˚C
Outdoor fan
Compressor
Содержание FTY25GXV1
Страница 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Страница 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Страница 11: ...Introduction SiBE01 829 x ...
Страница 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Страница 15: ...Functions SiBE01 829 4 List of Function ...
Страница 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Страница 19: ...Specifications SiBE01 829 8 Specifications ...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE01 829 12 Printed Circuit Board Connector Wiring Diagram ...
Страница 49: ...Instructions SiBE01 829 38 Operation Manual ...
Страница 69: ...Check SiBE01 829 58 Service Diagnosis ...
Страница 107: ...Outdoor Unit SiBE01 829 96 Removal Procedure 10 Remove the electrical box Step Procedure Points R8556 ...
Страница 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Страница 112: ...SiBE01 829 Others 101 Part 8 Others 1 Others 102 1 1 Trial Operation and Testing 102 1 2 Pump Down Operation 102 ...
Страница 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...
Страница 123: ...SiBE01 829 iv Drawings Flow Charts ...