Functions
SiBE01-829
18
Functions and Control
1.5
Programme Dry Function
Outline
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls airflow rate, the fan adjustment buttons are inoperable in this
mode.
Details of the
Control
During the first 12 minutes of the DRY mode run from:
1. After operation halt for 2 hours or more or
2. Mode change from HEAT, FAN or AUTO HEAT
DRY mode must run under cool mode with AUTO indoor fan for 12 minutes or until
room temp. < set temp. – 1°C.
After this, the DRY mode may run under either Zone A, B, C or D as below:
1. If room temp. – set temp. > 2°C, the operation is in Zone A
ZONE A
2. If 0°C < room temp. – set temp. < 1°C, then the operation is in Zone B.
ZONE B
3. If 1°C < set temp. – room temp. < 2°C, then the operation is in Zone C.
ZONE C
12 min.
ON
OFF
ON
OFF
Compressor
L tap
Time
Time
(R8491)
Compressor
L tap
ON
OFF
ON
OFF
8 min.
4 min.
30 sec.
30 sec.
(R8492)
Compressor
L tap
ON
OFF
ON
OFF
6 min.
6 min.
30 sec.
30 sec.
(R8493)
Содержание FTY25GXV1
Страница 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Страница 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Страница 11: ...Introduction SiBE01 829 x ...
Страница 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Страница 15: ...Functions SiBE01 829 4 List of Function ...
Страница 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Страница 19: ...Specifications SiBE01 829 8 Specifications ...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE01 829 12 Printed Circuit Board Connector Wiring Diagram ...
Страница 49: ...Instructions SiBE01 829 38 Operation Manual ...
Страница 69: ...Check SiBE01 829 58 Service Diagnosis ...
Страница 107: ...Outdoor Unit SiBE01 829 96 Removal Procedure 10 Remove the electrical box Step Procedure Points R8556 ...
Страница 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Страница 112: ...SiBE01 829 Others 101 Part 8 Others 1 Others 102 1 1 Trial Operation and Testing 102 1 2 Pump Down Operation 102 ...
Страница 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...
Страница 123: ...SiBE01 829 iv Drawings Flow Charts ...