SiBE01-829
Functions
Functions and Control
15
1.2
Fan Speed Control
for Indoor Units
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and Hall IC control.
For more information about
Hall IC
, refer to troubleshooting for fan motor on page 47.
Phase Steps
Phase control and fan speed control contains 5 steps: LL, L, M, H, and HH.
You can choose the airflow rate between LL and HH with the remote controller
= The airflow rate is chosen from L-M-H tap when the fan setting button is set to automatic.
Note:
1. During POWERFUL operation, fan operates at 1280-1370rpm.
2. Fan stops during defrost operation.
3. In time of thermostat OFF, the fan rotates at following speed.
Cooling : The fan keeps rotating at the set tap.
Heating : The fan stops when the indoor heat exchanger temperature is below 30°C.
Airflow Rate
Control
for
Heating
The following drawing explains the principle for fan speed control for heating:
Airflow Rate
Control for
Cooling
The following drawing explains the principle of fan speed control for cooling:
Step
LL (Quiet)
L
M
H
HH (POWERFUL)
Cooling
Heating
(R8509)
(R8510)
+3.0
L
M
H
Defference between
room and set
temperature
Phase control
Fan speed
+1.0
0
+2.0
(R8486)
H
M
L
Fan speed
Phase control
+1.5
+0.5
0.5
Defference between
room and set
temperature
(R8487)
Содержание FTY25GXV1
Страница 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Страница 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Страница 11: ...Introduction SiBE01 829 x ...
Страница 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Страница 15: ...Functions SiBE01 829 4 List of Function ...
Страница 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Страница 19: ...Specifications SiBE01 829 8 Specifications ...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE01 829 12 Printed Circuit Board Connector Wiring Diagram ...
Страница 49: ...Instructions SiBE01 829 38 Operation Manual ...
Страница 69: ...Check SiBE01 829 58 Service Diagnosis ...
Страница 107: ...Outdoor Unit SiBE01 829 96 Removal Procedure 10 Remove the electrical box Step Procedure Points R8556 ...
Страница 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Страница 112: ...SiBE01 829 Others 101 Part 8 Others 1 Others 102 1 1 Trial Operation and Testing 102 1 2 Pump Down Operation 102 ...
Страница 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...
Страница 123: ...SiBE01 829 iv Drawings Flow Charts ...