3.10 Defrost Control
Outline
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than a certain value to finish.
Detail
Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than A minutes (depending on the duration of the previous defrost control) of accumulated
time have passed since the start of the operation, or ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature L.
09/12 class
15/18 class
24 class
30/36 class
A (minutes)
15 ~ 28
15 ~ 44
15 ~ 38
15 ~ 38
B (Hz)
76
55
39
39
C (Hz)
86
90
62
62
D (seconds)
50
60
60
60
E (seconds)
60
120
120
120
F (seconds)
480
340
530
530
G (seconds)
60
50
60
60
H (pulse)
450
450
450
450
J (pulse)
350
450
300
350
K (pulse)
450
450
400
400
L
4 ~ 18°C
(39.2 ~ 64.4°F)
4 ~ 12°C
(39.2 ~ 53.6°F)
4 ~ 12°C
(39.2 ~ 53.6°F)
4 ~ 18°C
(39.2 ~ 64.4°F)
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz
B Hz
C Hz
5 sec.
J pulse
K pulse
H pulse
Initial opening
PI control
5 sec.
G sec.
(R16577)
Electronic expansion
valve opening
D sec.
E sec.
F sec.
Содержание FTXS30LVJU
Страница 8: ...SiUS091133 Table of Contents vii...
Страница 11: ...SiUS091133 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 FTXS Series 2 1 2 FDXS Series 4...
Страница 15: ...SiUS091133 5 Specifications Part 2 Specifications 1 Specifications 6 1 1 FTXS Series 6 1 2 FDXS Series 11...
Страница 164: ...SiUS091133 Check Service Diagnosis 154 15 18 class 24 30 36 class Power module R16697 R16073 Power module...
Страница 259: ...Indoor Unit FTXS30 36LVJU SiUS091133 249 Removal Procedure 6 Disconnect the connector Step Procedure Points R9558...
Страница 413: ...Wiring Diagrams SiUS091133 403 Appendix...