SiUS041829E
Troubleshooting
Part 6 Service Diagnosis
91
4.14 Input Overcurrent Detection
Error Code
E8
Method of Error
Detection
An input overcurrent is detected by checking the input current value with the compressor running.
Error Decision
Conditions
The current exceeds about 12.0 ~ 12.5 A (depending on the model) for 2.5 seconds with the
compressor running.
The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
Supposed
Causes
Outdoor temperature is out of operation range.
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit