4.6 Front Panel Open/Close Fault
Error Code
C7
Error Decision
Conditions
If the error repeats, the system is shut down.
Supposed
Causes
Defective reduction motor
Malfunction or deterioration of the front panel mechanism
Defective limit switch
Troubleshooting
You cannot operate the unit by the remote controller when the front panel mechanism breaks down.
<To the dealers: temporary measure before repair>
1. Turn off the power.
2. Remove the front panel.
3. Turn on the power.
(Wait until the initialization finishes.)
Operate the unit by the indoor unit
ON/OFF
switch.
YES
YES
YES
YES
NO
NO
NO
NO
Replace the harness and
red
u
ction motor.
Replace the assembly of the
front panel mechanism.
Check the movement of the
right and left separately by
hand.
Replace the assembly of the
front panel mechanism.
It is s
u
pposed s
u
ch as
deformation of the panel or
st
u
ffed d
u
st.
Find o
u
t the ca
u
se.
Replace the limit switch.
(R17249)
Caution
Does the front
panel move?
Does the front
panel mechanism
move?
Does the front
panel open/close f
u
lly?
Restart. Does the
error code reappear?
Restart and check the
movement.
Remove the front panel and
check the movement.
Be s
u
re to t
u
rn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание FTXR-T Series
Страница 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Страница 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Страница 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Страница 139: ...SiUS041829E Piping Diagrams Part 8 Appendix 135 1 2 Outdoor Unit RX09 12RMVJU9 RX18RMVJU9 3D092207C 3D092220C...
Страница 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...