10
■
English
Indoor Unit Installation
4-3. Wall embedded piping
• Insert the drain hose to this depth so it won’t be pulled out of the drain pipe.
5.
Wiring
1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut onto
the conduit mounting plate.
2) Strip wire ends (9/16 inch (15mm)).
3) Match wire colors with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the
corresponding terminals.
4) Connect the ground wires to the corresponding terminals.
5) Pull wires to make sure that they are securely latched up.
6) In case of connecting to an adapter system. Run the remote control cable and attach the S21.
7) Shape the wires so that the service lid fits securely, then close service lid.
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical
shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• When carrying out wiring connection, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
Inner wall
Vinyl chloride
drain pipe
(VP-30)
Drain hose
1-15/16” (50mm)
or more
Insert the drain
hose to this depth
so it won’t be pulled
out of drain pipe.
Outer wall
1
2
3
1 2 3
L
1
L
2
When wire length exceeds
33ft (10m), use AWG14 wires.
Outdoor unit
Indoor
unit
Use AWG16 or AWG14 wire
for the inter-unit wiring.
Shape wires so
that the service
lid will fit securely.
Terminal block
Electrical component box
Use the specified wire type.
Conduit
mounting
plate
Lock nut
Back
Conduit
01_EN_3P276866-2D.fm Page 10 Friday, February 18, 2011 4:07 PM