Control Specification
SiBE041401E
41
Function and Control
3.5
Input Current Control
Outline
The microcomputer calculates the input current while the compressor is running, and sets the
frequency upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of frequency and takes
priority over the lower limit control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
After 2.5 seconds in this zone, the compressor is stopped.
Dropping zone
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep
zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level
(depending on the model).
20/25 class
35 class
50 class
Cooling
Heating
Cooling
Heating
Cooling
Heating
A
(A)
9.25
9.25
20.0
B
(A)
6.25
7.5
8.25
12.0
C
(A)
5.5
6.75
7.5
11.0
Compressor Stop
Input current
Dropping Zone
Stop Zone
Keep Zone
Reset Zone
(R14643)
A
(A)
B
C
Содержание FTXG20LV1BW
Страница 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50...
Страница 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944...
Страница 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition...