Installation manual
Daikin room air conditioner
English
FTXF20E5V1BFTXF25E5V1BFTXF35E5V1BFTXF42E5V1B
Страница 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXF20E5V1B FTXF25E5V1B FTXF35E5V1B FTXF42E5V1B ...
Страница 2: ...тива и или регламент и при условие че продуктите се използват в съответствие с нашите инструкции atitinka toliau nurodytas direktyvas arba reglamentus su sąlyga kad gaminiai bus eksploatuojami laikantis mūsų instrukcijų atbilst šādām direktīvām vai regulām ja vien šie izstrādājumi tiek lietoti saskaņā ar mūsu instrukcijām sú v zhode s nasledujúcou imi smernicou ami alebo predpisom mi za predpoklad...
Страница 3: ...s are used in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 S I 2008 1597 Supply of Machinery Safety Regulations 2008 following the provisions of BS EN 60335 2 40 A B C TCF032E25 as set out in A and judged positively by B according to the Certificate C Daikin Europe N V is authoris...
Страница 4: ...run 15 10 2 1 To perform a test run in winter season 15 11 Disposal 15 12 Technical data 16 12 1 Wiring diagram 16 12 1 1 Unified wiring diagram legend 16 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin including all documents listed in Documentation set and in addition comply wi...
Страница 5: ... sucked in This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves befo...
Страница 6: ... them with bare hands DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST be less than 50 V DC before you can touch electrical components For the location of the terminals see the wiring diagram Finishing indoor unit installation see Finishing...
Страница 7: ...in and with applicable legislation and are executed ONLY by authorised persons 5 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Air flow Make sure nothing blocks the air flow Drainage Make sure condensation water can be evacuated properly Wall insulation When conditions in the wall exceed 30 C and a relative humidity of 80 or when fre...
Страница 8: ... and firmly engage the 3 upper hooks 2 Install 2 screws back on the front grille 3 Install the air filter and then mount the front panel 5 2 5 To remove the electrical wiring box cover 1 Remove the front grille 2 Remove 1 screw from the electrical wiring box 3 Open the electrical wiring box cover by pulling the protruding part on the top of the cover 4 Unhook the tab on the bottom and remove the e...
Страница 9: ...cover INFORMATION To connect the piping on right side right bottom left side or left bottom the pipe port cover MUST be removed 1 Cut off the pipe port cover from inside the front grille using a coping saw 2 Remove any burrs along the cut section using a half round needle file NOTICE Do NOT use nippers to remove the pipe port cover as this would damage the front grille 5 3 4 To provide drainage Ma...
Страница 10: ...ht side and install it on the left side 1 Remove the insulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug 3 Insert the drain hose on the left side and do n...
Страница 11: ...S use a spanner and torque wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm Ø6 4 15 17 8 7 9 1 R 0 4 0 8 2 45 90 2 ØA Ø9 5 33 39 12 8 13 2 6 2 2 To connect the refrigerant piping to the indoor unit WARNING M...
Страница 12: ...ithout thermal insulation as such pipes will be very hot 7 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are used twist the conductor to consolidate the end or twist the conductor to consolidate the end in combination with the usage of a round crimp style terminal on the end of the conductor Details are described in Guidelines wh...
Страница 13: ...a Drain hose b Interconnection cable c Mounting plate accessory d Refrigerant piping e Indoor unit fixing screw M4 12L accessory f Bottom frame 8 2 To pass the pipes through the wall hole 1 Shape the refrigerant pipes along the pipe path marking on the mounting plate a b c c d e a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate ...
Страница 14: ...mistors and or pressure sensors switches If NOT burning of the compressor might be the result 10 1 Checklist before commissioning 1 After the installation of the unit check the items listed below 2 Close the unit 3 Power up the unit You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted The outdoor unit is properly mounte...
Страница 15: ...The system stops operating 3 minutes after the unit is turned OFF 10 2 1 To perform a test run in winter season When operating the air conditioner in Cooling mode in winter set it to test run operation using the following method For FTXF and ATXF units 1 Press to switch the system on 2 Press the centre of and simultaneously 3 Press twice Result will appear on the display Test run operation is sele...
Страница 16: ... Meaning A P Printed circuit board BS Pushbutton ON OFF operation switch BZ H O Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse Symbol Meaning FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode HAP Light emitt...
Страница 17: ...r 3P650253 7H 2022 10 Symbol Meaning V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite core ZF Z F Noise filter ...