Control Specification
SiENBE12-713
84
Function and Control
2. Determine upper limit frequency
$
Set a minimum value as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipes, freeze-up protection, dew prevention,
fin thermistor temperature.
3. Determine lower limit frequency
$
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Pressure difference upkeep.
4. Determine prohibited frequency
$
There is a certain prohibited frequency such as a power supply frequency.
Indoor Frequency Command (
Δ
D signal)
The difference between a room temperature and the temperature set by the remote control will
be taken as the “
Δ
D signal” and is used for frequency command.
∗
Th OFF = Thermostat OFF
Indoor Unit Capacity (S value)
The capacity of the indoor unit is a “S” value and is used for frequency command.
Frequency Initial Setting
<Outline>
When starting the compressor, or when conditions are varied due to the change of the operating
room, the frequency must be initialized according to the total of a maximum
Δ
D value of each room
and a total value of Q (
Σ
Q) of the operating room (the room in which the thermostat is set to ON).
Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
PI Control (Determine Frequency Up / Down by
Δ
D Signal)
1. P control
Calculate a total of the
Δ
D value in each sampling time (20 seconds), and adjust the
frequency according to its difference from the frequency previously calculated.
2. I control
If the operating frequency is not change more than a certain fixed time, adjust the frequency
up and down according to the
ΣΔ
D value, obtaining the fixed
ΣΔ
D value.
When the
ΣΔ
D value is small...lower the frequency.
When the
ΣΔ
D value is large...increase the frequency.
3. Limit of frequency variation width
When the difference between input current and input current drooping value is less than 1.5
A, the frequency increase width must be limited.
4. Frequency management when other controls are functioning
$
When each frequency is drooping;
Frequency management is carried out only when the frequency droops.
$
For limiting lower limit
Frequency management is carried out only when the frequency rises.
Temperature
difference
Δ
D
signal
Temperature
difference
Δ
D
signal
Temperature
difference
Δ
D
signal
Temperature
difference
Δ
D
signal
0
∗
Th
OFF
2.0
4
4.0
8
6.0
C
0.5
1
2.5
5
4.5
9
6.5
D
1.0
2
3.0
6
5.0
A
7.0
E
1.5
3
3.5
7
5.5
B
7.5
F
Capacity
S value
Capacity
S value
2.5 kW
25
6.0 kW
60
3.5 kW
35
7.1 kW
71
5.0 kW
50
Содержание FTKS20D3VMW
Страница 11: ...Introduction SiENBE12 713 x...
Страница 47: ...Specifications SiENBE12 713 36 Specifications...
Страница 113: ...Control Specification SiENBE12 713 102 Function and Control...
Страница 122: ...SiENBE12 713 Instruction System Configuration 111 Names of Parts FTK X S 20 25 35 C Indoor Unit...
Страница 235: ...Instruction SiENBE12 713 224 System Configuration...
Страница 297: ...Check SiENBE12 713 286 Service Diagnosis...
Страница 316: ...SiENBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points...
Страница 330: ...SiENBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Control 320 1 2 Jumper Settings 321...