SiENBE12-713
Control Specification
Function and Control
97
Detail
Judgment by Input Current
When an output frequency is exceeds 55 Hz and the input current is less than specified value,
the adjustment is made for insufficient gas.
Judgment by Discharge Pipe Temperature
When discharge pipe temperature is 20°C higher than target value and the electronic expansion
value opening is 450 plus (max.), the adjustment is made for insufficient gas.
3.12.4 Preventing Indoor Freezing
During cooling, if the heat exchanger temperature in the operation stopped room becomes
below the specified temperature for the specified time, open the electronic expansion valve in
the operation stopped room as specified, and carry out the fully closed operation. After this, if
freezing abnormality occurs more than specified time, the system shall be down as the system
abnormality.
3.13 Forced Operation Mode
Outline
Forced operating mode includes functions such as; forced cooling, forced heating, incorrect
wiring, incorrect piping check.
Operating mode must be selected by operating the forced operation switch (SW1 on service
PCB).
Detail
Forced Cooling, Forced Heating (Only for Heat Pump Model)
Item
Forced Cooling
Forced Heating
Forced operation
allowing conditions
1) The indoor unit is not abnormal, but
the indoor unit which is not in the
freezing prohibiting zone is present in
more than 1 room.
1) The indoor unit is not abnormal.
The indoor unit which is not in the
peak-cut prohibited zone is present in
more than 1 room.
2) The outdoor unit is not abnormal
and not in the 3-minute stand-by
mode.
←
3) The operating mode of the outdoor
unit is the stop mode.
←
4) The slide selection switch of the
forced operation is the cooling mode.
The forced operation is allowed when
the above “and” conditions are met.
4) The slide selection switch of the
forced operation is the heating mode.
The forced operation is allowed when
the above “and” conditions are met.
Starting / adjustment If the forced operation switch is
pressed as the above conditions are
met.
←
1) Determine
operating room
All rooms
One of the available units runs.
Priority is given to the youngest
number’s room in alphabetical order.
(A
>
B
>
C
>
D)
2) Command
frequency
$
2YC45: 42 Hz
$
2YC45: 37 Hz
(Outdoor air temp:0°C)
3) Electronic
expansion valve
opening
It depends on the capacity of the
operating indoor unit.
←
4) Outdoor unit
adjustment
Compressor is in operation.
←
5) Indoor unit
adjustment
The command of forced operation is
transmitted to the indoor unit.
←
End
1) When the forced operation switch is
pressed again.
←
2) The operation is to end
automatically after 15 min.
←
Others
The protect functions are prior to all
others in the forced operation.
←
Содержание FTKS20D3VMW
Страница 11: ...Introduction SiENBE12 713 x...
Страница 47: ...Specifications SiENBE12 713 36 Specifications...
Страница 113: ...Control Specification SiENBE12 713 102 Function and Control...
Страница 122: ...SiENBE12 713 Instruction System Configuration 111 Names of Parts FTK X S 20 25 35 C Indoor Unit...
Страница 235: ...Instruction SiENBE12 713 224 System Configuration...
Страница 297: ...Check SiENBE12 713 286 Service Diagnosis...
Страница 316: ...SiENBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points...
Страница 330: ...SiENBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Control 320 1 2 Jumper Settings 321...