10
English
DRAIN PIPING WORK
Caution
Make sure all water is out before making the duct connection.
Install the drain piping.
• Make sure the drain works properly.
• The diameter of the drain pipe should be greater than or equal to the
diameter of the connecting pipe (vinyl tube; pipe size: 20mm; outer
dimension: 26mm).
• Keep the drain pipe short and sloping downwards at a gradient of at
least 1/100 to prevent air pockets from forming.
Caution
Water accumulating in the drain piping can cause the drain to clog.
• To keep the drain tube from sagging, space hanging wires every 1 to 1.5m.
• Use the drain hose and the metal clamp. Insert the drain hose fully into the drain socket and firmly tighten the metal clamp with
the upper part of the tape on the hose end. Tighten the metal clamp until the screw head is less than 4mm from the hose.
• The two areas below should be insulated because condensation may form there causing water to leak.
• Drain piping passing indoors
• Drain sockets
Referring the figure below, insulate the
metal clamp and drain hose using the
included large sealing pad.
PRECAUTIONS
Drain piping connections
• Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the
indoor unit through the drain pipes and corrode the heat exchanger.
• Do not twist or bend the drain hose, so that excessive force is not applied to it.
(This type of treatment may cause leaking.)
After piping work is finished, check drainage flows
smoothly. Gradually insert approximately 1L of
water into the drain pan to check drainage in the
manner described below.
• Gradually pour approximately 1L of water from the
outlet hole into the drain pan to check drainage.
• Check the drainage.
Caution
When filling the drainpan with water, be sure that the water is sliding down the drainpan wall (see picture above).
Failure to observe this instruction may result in water leakage.
Connect the drain pipe after
removing the rubber cap and
insulation tubing attached to
the connection hole.
Refrigerant pipes
Drain pipe connection hole
(accessory)
Tape
Drain hose
Clamp metal
(accessory)
(accessory)
Clamp metal
Large sealing pad
≤4mm
Portable pump
Bucket
Drain pan
Air outlet
Drain outlet
Refrigerant
pipes