SiBE28-804
General Functionality
Functional Description
51
1.15 Preheating Operation Control
RZQ71C7, RZQS71·100C7V1B
Outline
After the compressor has been turned off, the preheating operation will be activated in order to
avoid refrigerant from dissolving in the compressor oil.
Trigger
conditions
Starting conditions
• Compressor stopping
&
&
or
• Less than 6 hours duration after turning on the power.
• Longer than 1 hour elasped after shutting down the compressor.
• Outside temperature is not declining.
• Discharge pipe temperature < 70˚C
Ending conditions
• Operation of thermostat is established
{
{
{
&
{
{
{
or
&
• Longer than 6 hours elasped after turning on the power.
• Less than 1 hour duration after shutting down the compressor.
• Outside temperature is declining.
• Discharge pipe temperature > 75˚C
Содержание FHQ100BUV1B x 2
Страница 1: ...SiBE28 804 SkyAir RZQ71C7V1B RZQ100 140C7V1B RZQS71 100C7V1B RZQS125 140C7V1B R 410A Heat Pump 50Hz ...
Страница 13: ...SiBE28 804 2 ...
Страница 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Страница 29: ...Specifications SiBE28 804 18 Specifications ...
Страница 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Страница 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Страница 43: ...SiBE28 804 32 Functional Description 6 Outdoor Unit Fan Speed Control 81 6 1 Outdoor Unit Fan Speed Control 81 ...
Страница 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Страница 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Страница 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Страница 277: ...PCB Layout SiBE28 804 266 Appendix ...
Страница 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...
Страница 311: ...SiBE28 804 iv Index ...