Control Specification
SiUS091628EA
39
Functions and Control
2.10 Defrost Control
Outline
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than a certain value to finish defrosting.
Details
Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than
A
minutes (depending on the duration of the previous defrost control) of accumulated
time have passed since the start of the operation, or ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature (
B
).
09/12 class
15/18 class
A
(minute)
20 ~ 25
25
B
(°C)
2 ~ 20
6 ~ 30
(°F)
35.6 ~ 68.0
42.8 ~ 86.0
C
(Hz)
64
48
D
(Hz)
64
42
E
(seconds)
40
60
F
(seconds)
60
60
G
(seconds)
510
340
H
(seconds)
50
60
J
(seconds)
8
5
K
(pulse)
400
450
L
(pulse)
300
300 ~ 450
M
(pulse)
350
300
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz
0 Hz
C
Hz
D
Hz
J
sec.
PI control
8 sec.
H
sec.
(R21661)
E
sec.
F
sec.
G
sec.
L
pulse zone
Electronic
expansion valve
opening
Normal
control
K
pulse
zone
M
pulse
zone
Starting
control
Содержание FFQ09Q2VJUFFQ12Q2VJUFFQ15Q2VJUFFQ18Q2VJURX09QMVJURX12QMVJURX15QMVJURX18QMVJU
Страница 12: ...SiUS091628EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiUS091628EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 120: ...Check SiUS091628EA 109 Service Diagnosis 15 18 class R20701 1 2 3 4 Multimeter...
Страница 122: ...Check SiUS091628EA 111 Service Diagnosis 15 18 class R20704 W V U DC_P1 DC_N1...