SiSG121917E
MSP Duct Type Functions
Part 4 Functions and Control
64
2. MSP Duct Type Functions
2.1 Drain Pump Control
Normal Operation
The float switch is ON in normal operation.
When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
The aim of residual operation after thermostat OFF is to eliminate the dew that condenses
on the indoor heat exchanger during cooling operation.
If Float Switch is ON with Thermostat ON in Cooling Operation
When the float switch turns OFF, the thermostat turns OFF simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
Notes:
1. If the float switch turns ON again during the residual operation of the drain pump, cooling
operation also turns on again (thermostat ON).
2. If the float switch remains OFF even after the residual operation of the drain pump has
ended, the error code
A3
is displayed on the remote controller.
3. The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
4. After
A3
is displayed and the unit comes to an abnormal stop, the thermostat will remain OFF
even if the float switch turns ON again.
Float s
w
itch
Error display
Thermostat
(r
u
nning)
OFF
OFF
O
N
O
N
O
N
OFF
Drain p
u
mp
O
N
OFF
5 min.
(R24669)
OFF
OFF
O
N
O
N
O
N
OFF
O
N
OFF
5 min.
5 min. 5 sec.
5 sec.
(R24670)
Float s
w
itch
Error display
Thermostat
(r
u
nning)
Drain p
u
mp
A3
}
∗
1
∗
2
∗
4
∗
3
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...