Field Settings
SiSG121917E
201
Part 7 Trial Operation and Field Settings
5.3.2 NIGHT QUIET Mode
Outline
If NIGHT QUIET mode is to be used, initial settings must be made when the unit is installed.
Explain the function of NIGHT QUIET mode, as described below, to the customer, and confirm
whether or not the customer wants to use NIGHT QUIET mode.
NIGHT QUIET mode function reduces operating noise of the outdoor unit at nighttime. This
function is useful if the customer is worried about the effects of the operating noise on the
neighbors. However, if NIGHT QUIET mode is running, cooling capacity is reduced.
Details
Slide the SW6-1/SW5-5 to the ON side.
5.3.3 Limitation Setting for Input Current
Outline
You can select an upper limit for the input current. Use the operation mode switch (SW2) and
the NIGHT QUIET mode setting switch (SW6-1 or SW5-5) to set the upper limit.
50/65/80 class
90 class
Ser
v
ice monitor PCB
HEAT
COOL
A
1
2
3
4
5
2
1
D
C
B
A
N
IGHT QUIET mode
setting s
w
itch
(S
W
6-1)
2
1
O
N
OFF
4
3
2
1
(R24956)
S2
S502
A
1
2
3
4
5
HEAT COOL
OFF
O
N
O
N
OFF
1234
5
Ser
v
ice monitor PCB
O
N
OFF
N
IGHT QUIET mode
setting s
w
itch (S
W
5-5)
1 2 3 4 5
(R24957)
50/65/80 class
90 class
R7000257
R7000258
SW2
SW6-1
Service monitor PCB
Service monitor PCB
SW5-5
SW2
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...