Field Settings
SiSG121917E
193
Part 7 Trial Operation and Field Settings
5.2 MSP Duct Type Indoor Unit
5.2.1 Field Settings with BRC086A22 Wireless Remote Controller
Outline
When optional accessories are mounted on the indoor unit, the indoor unit setting may have to
be changed. Refer to the instruction manual for each optional accessory.
Procedure
With BRC086A22 Remote Controller
1. When in the normal mode, press
INSPECTION
button for 4 seconds or more, and the FIELD
SET MODE is entered.
2. Select the desired MODE NO. with
MODE
button.
3. Press
FAN
button and
BACK LIGHT
button and select the FIRST CODE NO.
4. Press
TEMP
button and select the SECOND CODE NO.
5. Press
RESERVE
button and the present settings are SET.
6. Press
INSPECTION
button to return to the NORMAL MODE.
MODE NO.
FIRST
CODE NO.
SECOND
CODE NO.
5
2
1, 6
4
3
(R24950)