Field Settings
SiSG121917E
191
Part 7 Trial Operation and Field Settings
Caution
5. Field Settings
5.1 Wall Mounted and LSP Duct Type Indoor Unit
5.1.1 When 2 Units are Installed in 1 Room
Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding
wireless remote controller can be set for different address.
Wall Mounted
Type
1. Remove the battery cover on the remote controller and cut the address jumper (J4).
2. Press the center of
Temp
button and
Mode
button at the same time.
3. Press
Temp
button, select
A
, press
Mode
button.
The indoor unit operation lamp will blink for about 1 minute.
4. Press the indoor unit
ON/OFF
switch while the operation lamp is blinking.
If setting could not be carried out completely while the operation lamp was blinking, carry
out the setting process once again from the beginning.
After setting is complete, pressing
Mode
button for about 5 seconds will cause the
remote controller to return to the previous display
Replace the remote controller if you cut a jumper unintentionally
.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Wireless Remote Controller
Indoor Unit
r7000041
Temp
bu
tton
Mode
bu
tton
(R24702)
(R22634)
Jumper
ADDRESS
J4
EXIST
CUT
1
2
J4
ON/OFF
Operation
lamp
Indoor unit
ON/OFF
switch
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...