Part 6 Service Diagnosis
170
Note
8.2 Indoor Fan Motor Connector Check
Check No.03
Fan motor wire breakdown/short circuit check
(1) Check the connector for connection.
(2) Turn the power off.
(3) Check if each resistance at the phases U - V and V - W is within specified range in the
table below.
Motor control voltage check
(1) Check the connector for connection.
(2) Check the motor control voltage is generated (between the pins 2 - 3).
Rotation pulse check
(1) Check the connector for connection.
(2) Turn the power on and stop the operation.
(3) Check if the Hall IC generates the rotation pulse 4 times when the fan motor is manually
rotated once (between the pins 1 - 3).
R6000090
A measurement error might occur in the resistance value depending on the measurement
conditions and the method.
U-V/V-W Resistance (
)
Wall mounted
25/35/50 class
72.7 ~ 78.8
Wall mounted
60/71 class
42.9 ~ 46.6
12
11
10
9
8
7
6
5
4
3
2
1
Phase U
Free pin
Free pin
Free pin
Free pin
Free pin
Free pin
Phase V
Phase W
GND
Motor control voltage (15 VDC)
Rotation pulse (5 VDC)
S200
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...