7.18 Thermistor or Related Abnormality (Outdoor Unit)
Error Code
H9
,
J3
,
J6
,
J8
,
J9
,
P4
Outdoor Unit LED
Display
A
j
1
i
2
i
3
h
4
h
5
h
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The voltage between the both ends of the thermistor is above 4.96 V or below 0.04 V with
the power on.
J3
error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
The system is shut down if all the units are judged as the
J8
error.
Supposed
Causes
Disconnection of the connector for the thermistor
Thermistor corresponding to the error code is defective.
Defective heat exchanger thermistor in the case of
J3
error
Defective outdoor unit PCB
Troubleshooting
In case of
P4
Replace the outdoor unit PCB (main PCB).
P4
: Radiation fin thermistor
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...