Troubleshooting for MSP Duct Type Indoor Unit
Part 6 Service Diagnosis
136
6.9 Signal Transmission Error (Between MAIN Remote
Controller and SUB Remote Controller)
Error Code
U8
Method of Error
Detection
In case of controlling with 2 remote controllers, check the system using microcomputer if signal
transmission between MAIN remote controller and SUB remote controller is normal.
Error Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Remote controller is set to SUB when using 1 remote controller
Connection of 2 SUB remote controllers (when using 2 remote controllers)
Defective remote controller PCB
Troubleshooting
Is SS1
of remote
controller PCB set to
SUB?
T
u
rn the po
w
er off and then
b
ack on. If a malf
u
nction occ
u
rs,
replace the remote controller
PCB.
T
u
rn the po
w
er off and then
b
ack on. If a malf
u
nction occ
u
rs,
replace the remote controller
PCB.
Set one remote controller to
MAI
N
; t
u
rn the po
w
er s
u
pply off
once and then
b
ack on.
Set SS1 to MAI
N
; t
u
rn the
po
w
er s
u
pply off once and then
b
ack on.
YES
N
O
YES
N
O
N
O
YES
(R21113)
Using 2 remote
controllers?
Is SS1 of
b
oth
remote controllers
set to SUB?
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...