Troubleshooting for MSP Duct Type Indoor Unit
SiSG121917E
129
Part 6 Service Diagnosis
6.3 Indoor Fan Motor or Related Abnormality
Error Code
A6
Method of Error
Detection
Detection from the current flow on the fan PCB
Detection from the rotation speed of the fan motor in operation
Error Decision
Conditions
The rotation speed is less than a certain level for 6 seconds.
Supposed
Causes
Clogged foreign matter
Disconnection of fan motor connectors
Disconnection of the connector between the indoor unit PCB and the fan PCB
Defective fan PCB
Defective fan motor
No fuse continuity
Trouble Shooting
Connect the connector
correctly.
T
u
rn OFF the po
w
er s
u
pply
and
w
ait for 10 min
u
tes.
N
O
T
u
rn O
N
the po
w
er s
u
pply
w
hile
the fan motor connector (
∗
1) is
disconnected.
YES
N
O
Connect the connector
correctly.
N
O
YES
YES
Replace the f
u
se.
There is a
contin
u
ity in the f
u
se
(
∗
2) on the fan PCB or fan
motor harness.
N
O
The fan motor
connector (
∗
1) is
connected to the fan
PCB.
Remo
v
e the foreign matter.
YES
There is a foreign
matter aro
u
nd the fan.
The connector
b
et
w
een the indoor
u
nit
main PCB and the fan PCB
is connected.
A
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
(R24936)
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...