Functions for FTX, FVXS Series
SiUS091601EA
57
Part 4 Functions and Control
Note(s)
Note(s)
For dry operation, the temperature cannot be set with a remote controller, but the target
temperature is shifted internally.
2.10 POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, the air conditioner can be operated
by increasing the indoor fan rotating speed and the compressor frequency.
Details
When
POWERFUL
button is pressed, the fan speed and target temperature are converted to the
following states for 20 minutes.
Ex: POWERFUL operation in cooling
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW, or
OUTDOOR UNIT QUIET operation.
Operation mode
Fan speed
Target temperature
COOL
H tap +
A
rpm
18°C (64.4°F)
DRY
Dry rotating speed +
A
rpm
Lowered by 2.5°C (4.5°F)
HEAT
H tap +
A
rpm
B
FAN
H tap +
A
rpm
—
AUTO
Same as cooling/heating in
POWERFUL operation
The target temperature is kept
unchanged.
A
= FTX09/12/15NMVJU: 80 (rpm)
FTX18/24UVJU: 50 (rpm)
FVXS series: 30 ~ 40 (rpm)
B
= FTX09/12/15NMVJU: 31°C (87.8°F)
FTX18/24UVJU: 31.5°C (88.7°F)
FVXS series: 32°C (89.6°F)
(R24589)
Target temp.
Fan
A
rpm
H tap
Set tap
20 minutes
Lower limit of cooling
temperature
Remote controller registers
20 minutes independently.
POWERFUL
ON
POWERFUL
OFF
Ending conditions:
1. Lapse of 20 minutes
2. System operation OFF
3. POWERFUL operation OFF
18°C (64.4°F)
Содержание FDMQ12RVJU
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181 ...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185 ...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190 ...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191 ...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter ...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A ...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...